System Set-Up
Installation Manual
79
ENGLISH
Code
Item
Detail
Remark
05
Function
Setting temperature selection
Description
Selection for setting temperature as air temperature or
leaving water temperature.
Value #1
Note
01:Air temperature
02:Leaving water temperature
Air temperature as setting temperature is ONLY available
when remote air sensor.
Connection is enabled and Function code 03 is set as 02.
Default
2
Range
01 ~ 02
Value #2
Note
-
Default
-
Range
-
06
Function
Auto dry contact
Description
Setting dry contact auto start option.
If thermostat is used, value should be changed from "2" to "1".
Value #1
Note
01: Auto start off
02: Auto start on
Default
2
Range
01 ~ 02
Value #2
Note
-
Default
-
Range
-
07
Function
Address setting
Description
Assigning address when central controller is installed
If thermostat is used, value should be changed from "2" to "1".
Value #1
Note
-
Default
00
Range
00 ~ FF
Value #2
Note
-
Default
-
Range
-
11
Function
Setting air temperature in cooling mode
Description
Adjusting range of 'Setting Air Temperature' in cooling mode
Value #1
Note
Upper limit of setting range
Default
30 °C
Range
24 ~ 30 °C
Value #2
Note
Lower limit of setting range
Default
18 °C
Range
18 ~ 22 °C
12
Function
Setting leaving water temperature in cooling mode
Description
Adjusting range of 'Setting Leaving Water Temperature' in
cooling mode
Value #1
Note
Upper limit of setting range
Default
24 °C
Range
20 ~ 25 °C
'Setting Air
Temperature' is
used when user
wants to set target
temperature by
room air
temperature.
'Setting Leaving
Water Temperature'
is used when user
wants to set target
temperature by
leaving(from the
unit) water
temperature.