Code
Item
Detail
Remark
Note
Starting date (Sunday:1,Monday:2, ···· ,Saturday:7)
Default
06
Range
01 ~ 07
Value #2
Value #1
Note
Starting time in 24 hours(00 ~ 23)
Default
23
Range
00 ~ 23
27
Function
Setting pasteurisation Operation
Description
Setting pasteurisation temperature
Value #1
Note
Maximum heating temperature
Default
70 °C
Range
40 ~ 80 °C
Value #2
Note
Maximum heating duration in minute
Default
10 min
Range
05 ~ 60 min
28
Function
Setting control parameter for Domestic hot water heating operation
Description
See below notes for each values
Value #1
Note
Temperature gap from Value #2 of Function Code 28
Default
05 °C
Range
01 ~ 20 °C
Value #2
Note
Maximum temperature generated by AWHP compressor cycle
Default
48 °C
Range
40 ~ 48 °C
29
Function
Setting control parameter for Domestic hot water heating operation
Description
See below notes for each values
Value #1
Note
Temperature gap from target Domestic hotwater temperature
.
(This value is required to frequent ON and OFF of water tank heater.)
Default
03 °C
Range
02 ~ 04 °C
Value #2
Note
Determining heating demand priority between Domestic hot water tank
heating and under floor heating
Default
00 : Sanitary water tank priority
Range
01 : under floor heating
Only available
when Domestic
hot Water
Tank is installed.
• To use
disinfection mode,
Domestic hot water
heating should be
enable.
25
Function
Setting Heating flow temperature range for weather-dependent operation
Description
Setting Heating flow max / min temperature for
weather-dependent operation
Value #1
Note
Upper limit of setting range
Default
57 °C
Range
35 ~ 57 °C
Value #2
Note
Lower limit of setting range
Default
15 °C (*20 °C)
Range
15 ~ 34 °C (*20 ~ 34 °C)
26
Function
Setting pasteurisation operation
Description
Setting start/maintain time for pasteurisation
Value #1
Note
Enable / Disable of pasteurisation operation(00:Disable , 01:Enable)
Default
00
Range
00 ~ 01
Domestic hot water
* : Electric heater
is not used.
heating should be
enable.
• If Domestic hot
water heating is
disable, the disinf-
ectionmode will not
beoperated although
Value #1 of Code26
is set as '01'.
System Set-Up
82