Check Points, Maintenance and Troubleshooting
To assure best performance of , it is required to perform periodical check and maintenance.
It is recommended to proceed following check list for once a year.
Maintenance
Turn off the power before proceeding maintenance
CAUTION
During test operation in winter, it will drive the heating operation focused.
Before cooling test operation, to concern freezing of the plate heat exchanger, performing
the cooling test operation after raising the water temperature up to 30℃ in the heating
mode.
CAUTION
• In normal state, the pressure gage (in front of the indoor unit) should
indicate 2.0~2.5 bar.
• If the pressure is less than 0.3 bar, please recharge the water.
• Close the shut-off valves and disassemble strainer. Then wash the
strainer to make it clean.
• While disassembling the strainer, be careful for water flood out.
• Open the switch of the safety valve and check if water is flood out
through the drain hose.
• After checking, close the safety valve.
• Look and inspect if there is loosen or defected connection on the
terminal block.
No Category Item Check Point
Water
Electricity
Water pressure
Strainer(Water filter)
Safety valve
Terminal block wiring
1
2
3
4
Installation Manual
93
ENGLISH
Test Run
1
Check to see whether there is any refrigerant leakage, and check whether the power or
transmission cable is connected properly.
2
Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal
block and ground. Do not operate in the case of 2.0 MΩ or less.
NOTE
: Never carry out mega ohm check over terminal control board.
Otherwise the control board may break.
Immediately after mounting the unit or after leaving it turned off for an extended
length of time, the resistance of the insulation between the power supply
terminal board and the ground may decrease to approx. 2.0 MΩ as a result of
refrigerant accumulation in the internal compressor.
If the insulation resistance is less than 2.0 MΩ, turn on the main power supply.
Check before Test run