INSTALLER’S SETTING OPTIONS
219
ENGLISH
218
INSTALLER’S SETTING OPTIONS
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
Select remote controller Celsius control unit setting code value ‘15’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
In value1, use ‘
▲
’, ‘
▼
’ button to select ventilation standard fan speed setting value, and press
‘Done’ button to complete the setting.
- If you do not press ‘Done’ button, the setting value will not be applied.
Ventilator Fan Speed Alignment (General ventilator)
It is the function to change the standard fan speed of the ventilation product.
h
Ventilation standard wind amount setting value
- 00: factory ship-out
- 01: 10% increase
- 21: 10% decrease
- 22: 20% decrease
h
If there is no button input for about 60 seconds after the setting, it automatically exits from the
setting mode.
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
Select remote controller Celsius control unit setting code value ‘14’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
In value1, use ‘
▲
’, ‘
▼
’ button to select ventilation heating humidification setting value, and
press ‘Done’ button to complete the setting.
- If you do not press ‘Done’ button, the setting value will not be applied.
Humidification Of Ventilation With Heating Operation (DX type ventilator)
It is the function to set the heating humidification function of the direct ventilation to be auto-
matic or manual.
h
Ventilation single humidification setting value
- 01: Used
- 02: Not used
h
If there is no button input for about 60 seconds after the setting, it automatically exits from the
setting mode.