Fan Coil Unit
Installation
CAUTION:
Ceiling
Drainage hole
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
Lay the drain hose with a downward
inclination so water will drain out.
CORRECT
INCORRECT
CORRECT
INCORRECT
Front of view
1-3 mm
1. Install declination of the unit is very important for the drain of the duct type unit.
2. Minimum thickness of the insulation for the connecting pipe shall be 20mm.
• The unit must be horizontal or declined to the drain hose connected when finished installation.
• Always lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any
part.
• 5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.