Specifications 

Connection Type  

Series connected

Agency Listings 

UL 1449, UL 1283, CSA

Protection Modes 

All modes standard (Line to Neutral, 

Line to Ground, Neutral to Ground, 

Line to Line); any combination optional

EMI/RFI Filtering 

Normal mode — 60 dB maximum from 

10 kHz to 500 MHz; Common mode 

50 dB maximum from 10 kHz to 500 MHz

Response Time 

less than .5 nanoseconds

Load Regulation 

1% no load to full load

Enclosure 

NEMA 12 standard; options include 

NEMA 3R, 4, 4X and caseless for 

switchgear applications

Current

Model Number

Surge Current Capability

Dimensions

Rating

Configuration

(xxx=voltage code)

per phase (L-N or L-L+L-G)

(inches)

Weight

A

B

C

D

E

F

Lbs.

30A 

Single Phase L-L

FXXXL30

100kA

24.0

20.0

9.0

21.25

10.0

.44

40

30A

Single Phase L-N

FXXXN30 

100kA

24.0

20.0

9.0

21.25

10.0

.44

35

30A

Split Phase

FXXXS30

100kA

24.0

20.0

9.0

25.25

14.0

.44

45

30A

Three Phase Delta

FXXXD30

100kA

24.0

20.0

9.0

25.25

14.0

.44

50

30A

Three Phase Wye

FXXXY30

100kA

24.0

20.0

9.0

25.25

14.0

.44

60

60A

Single Phase L-L

FXXXL60

100kA

24.0

20.0

9.0

21.25

10.0

.44

40

60A

Single Phase L-N

FXXXN60

100kA

24.0

20.0

9.0

21.25

10.0

.44

35

60A

Split Phase

FXXXS60

100kA

24.0

20.0

9.0

25.25

14.0

.44

45

60A

Three Phase Delta

FXXXD60

100kA

24.0

20.0

9.0

25.25

14.0

.44

50

60A

Three Phase Wye

FXXXY60

100kA

24.0

20.0

9.0

25.25

14.0

.44

60

100A

Single Phase L-L

FXXXL100

150kA

30.0

24.0

9.0

31.25

18.0

.44

65

100A

Single Phase L-N

FXXXN100

150kA

30.0

24.0

9.0

31.25

18.0

.44

60

100A

Split Phase

FXXXS100

150kA

30.0

24.0

9.0

31.25

18.0

.44

70

100A

Three Phase Delta

FXXXD100

150kA

30.0

24.0

9.0

31.25

18.0

.44

70

100A

Three Phase Wye

FXXXY100

150kA

30.0

24.0

9.0

31.25

18.0

.44

80

125A

Single Phase L-L

FXXXL225

150kA

30.0

24.0

9.0

31.25

18.0

.44

65

125A

Single Phase L-N

FXXXN225

150kA

30.0

24.0

9.0

31.25

18.0

.44

60

225A

Split Phase

FXXXS225

150kA

30.0

24.0

9.0

31.25

18.0

.44

70

225A

Three Phase Delta

FXXXD225

150kA

30.0

24.0

9.0

31.25

18.0

.44

70

225A

Three Phase Wye

FXXXY225

150kA

30.0

24.0

9.0

31.25

18.0

.44

80

400A

Three Phase Delta

FXXXD400

150kA

48.0

36.0

12.0

49.25

30.0

.44

275

400A

Three Phase Wye

FXXXY400

150kA

48.0

36.0

12.0

49.25

30.0

.44

300

800A

Three Phase Delta

FXXXD800

choose 200 or 300 kA

60.0

48.0

12.0

-

-

-

500

800A

Three Phase Wye

FXXXY800

choose 200 or 300 kA

60.0

48.0

12.0

-

-

-

530

1200A

Three Phase Delta

FXXXD1200

choose 200 or 300 kA

60.0

48.0

20.0

-

-

-

700

1200A

Three Phase Wye

FXXXY1200

choose 200 or 300 kA

60.0

48.0

20.0

-

-

-

750

2000A

Three Phase Delta

FXXXD2000

choose 200 or 300 kA

60.0

48.0

20.0

-

-

-

875

2000A

Three Phase Wye

FXXXY2000

choose 200 or 300 kA

60.0

48.0

20.0

-

-

-

950

4000A

Three Phase Delta

FXXXD4000

choose 200 or 300 kA

60.0

48.0

20.0

-

-

-

1175

4000A

Three Phase Wye

FXXXY4000

choose 200 or 300 kA

60.0

48.0

20.0

-

-

-

1300

How To Specify The Appropriate Model:

1) Go to Chart A, choose your Current Rating from column one and corresponding Configuration from column two.

2) Follow column two across to column three to determine your Model Number.

3) Refer to Chart B to determine the Voltage Code from the available choices. Substitute the Voltage Code for “XXX.” 

(Use the first three digits of the Voltage Code for split phase and three phase configurations).

4) Finally, to complete your model number, go to the last column or (Monitoring Options) and choose the suffix for Standard Features (-06) or

Optional Features (-03).

Char t A - Active Tracking

®

Filter Systems

Char t B - Nominal Voltage Codes

(substitute for “xxx” to complete model number)

Single Phase, 2 wire plus ground

100, 110, 120, 230, 240, 277, 346, 400, 480, 600

Split Single Phase, 3 wire plus ground

100/173, 110/190, 120/208 or 240, 230/400, 277/480, 346/600

Three Phase Delta, 3 wire plus ground

208, 240, 380, 400, 480, 600

Three Phase Delta Hi-Leg, 4 wire plus ground

120/240

Three Phase Wye, 3 or 4 wire plus ground

100/173, 110/190, 120/208, 230/400, *277/480, 346/600

A

D

F

E

B

- Diameter

C

- Optional Features
   2.0” MAX
- Standard Features
   .50” MAX

Line Frequency 

47 to 63 Hz

Line Voltage

±15% nominal

Temperature 

-40 to +60°C

Operating Humidity 

0 to 95% noncondensing

Altitude 

0 to 18,000 feet

Audible Noise

Less than 45 dBa

Operational Crest Factor  3.0

Warranty

10-Years Parts and 

5-Years On-Site Labor

Monitoring 

Options

Standard Features Include:

•Audible Alarm, 

Transient Counter

• Door LEDs indicating

unit status

• Individual Module

Status LEDs, and

-06

Form C Dry Contacts
for Remote System
Integrity Monitoring
and Indication of
Under Voltage, Phase
and/or Power Loss.

Optional Features Include:

• Additional Seven-

Digit Transient Counter
for Normal Mode

-03

• Additional Form C

Dry Contacts

NOTES: For configurations not
mentioned, including caseless
units for switchgear applications
and ungrounded delta units, 
consult factory. For different levels 
of surge current capacity mode
and/or phase, consult factory.

CODE: 
L - N = Line to Neutral
L - G = Line to Ground
N - G = Neutral to Ground
L - L = Line to Line

*Valid for 220/380 and 
240/415 per IEC.

Example Model Number:

F120Y30-03