background image

10 

 

3-4. Single UPS Operation 

1. Turn on the UPS with utility power supply (in AC mode)   

1)    After power supply is connected correctly, set the breaker of the battery pack at 

“ON” position (the step 

only available for long-run model). Then set the input breaker at 

“ON” position. At this time the fan is 

running  and  the  UPS  supplies  power  to  the  loads via  the  bypass.  The UPS  is  operating  in  Bypass 

mode.   

NOTE: 

When UPS is in Bypass mode, the output voltage will directly power from utility after you switch 

on  the  input  breaker.  In  Bypass  mode,  the  load  is  not  protected  by  UPS.  To  protect  your  precious 

devices, you should turn on the UPS. Refer to next step.   

2)    Press and hold 

the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.     

3)  A  few  seconds  later,  the  UPS  will  enter  to  AC  mode.  If  the  utility  power  is  abnormal,  the  UPS  will 

operate in Battery mode without interruption. 

NOTE: 

When the UPS is running out battery, it will shut down automatically at Battery mode. When the 

utility power is restored, the UPS will auto restart in AC mode.   

2. Turn on the UPS without utility power supply (in Battery mode) 

1)    Make sure that the breaker of the battery pack is at 

“ON” position (only for long-run model).   

2)    Press and hold 

the “ON” button for 0.5s to turn on the UPS, and the buzzer will beep once. 

3)    A few seconds later, the UPS will be turned on and enter to Battery mode. 

3. Connect devices to UPS 

After the UPS is turned on, you can connect devices to the UPS. 

1)    Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load 

level.   

2)    If  it  is  necessary  to  connect  the  inductive  loads  such  as  a  printer,  the  in-rush  current  should  be 

calculated carefully to see if it meets the capacity of the UPS, because the power consumption of this 

kind of loads is too big. 

3)    If the UPS is overload, the buzzer will beep twice every second. 

4)    When the UPS is overload, please remove some loads immediately. It is recommended to have the 

total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for 

system safety.   

5)    If  the  overload  time  is  over  acceptable  time  listed  in  spec  at  AC  mode,  the  UPS  will  automatically 

transfer to Bypass mode.    After the overload is removed, it will return to AC mode. If the overload 

time is over acceptable time listed in spec at Battery mode, the UPS will become fault status. At this 

time, if bypass is enabled, the UPS will power to the load via bypass. If bypass function is disabled or 

the input power is not within bypass acceptable range, it will cut off output directly. 

4. Charge the batteries 

1)    After  the  UPS  is  connected  to  the  utility  power,  the  charger  will  charge  the  batteries  automatically 

except in Battery mode or during battery self-test.   

2)    Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter 

than expected time. 

Summary of Contents for Adapt BX 10K

Page 1: ...Single Phase Online UPS Liebert Adapt BX User Manual 6k 10kVA...

Page 2: ...4 UPS Installation for Parallel System 6 2 5 Software Installation 6 3 Operations 7 3 1 Button Operation 7 3 2 LED Indicators and LCD Panel 7 3 3 Audible Alarm 9 3 4 Single UPS Operation 10 3 5 Parall...

Page 3: ...for ventilation UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualifie...

Page 4: ...000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 3 Low Frequency Signals IEC EN 61000 2 2 W...

Page 5: ...lug One parallel cable only available for parallel model One share current cable only available for parallel model NOTE Before installation please inspect the unit Be sure that nothing inside the pack...

Page 6: ...as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all...

Page 7: ...ry The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for long run model Make sure a DC breaker or other prote...

Page 8: ...g to the section 2 3 2 Connect the output wires of each UPS to an output breaker 3 Connect all output breakers to a major output breaker Then this major output breaker will directly connect to the loa...

Page 9: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press t...

Page 10: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 11: ...lt mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO enable Fan failure Over temperature Charger failur...

Page 12: ...rned on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel...

Page 13: ...7 LCD setting section 6 Test the batteries 1 If you need to check the battery status when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery se...

Page 14: ...t off you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the input breaker and switch off the battery breaker...

Page 15: ...the parallel models and follow the wiring refer to section 2 3 3 Install the new parallel system refers to the previous section 3 Remove one unit from the parallel system 1 If the bypass is abnormal...

Page 16: ...B Subtract ADD Add ON On OFF Off FBD Not allowed OPN Allow RES Reserved 3 7 LCD Setting There are three parameters to set up the UPS Refer to following diagram Parameter 1 It s for program alternative...

Page 17: ...tput voltage in parameter 3 208 Presents output voltage is 208Vac 220 Presents output voltage is 220Vac 230 Presents output voltage is 230Vac 240 Presents output voltage is 240Vac 02 Output frequency...

Page 18: ...e default value is 110V Parameter 3 Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V 04 Frequency range for bypass Interface Setting Paramete...

Page 19: ...Hz 08 Bypass mode setting Interface Setting Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected i...

Page 20: ...battery 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage range is from 0V to 5 7V the default va...

Page 21: ...output for energy saving LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery...

Page 22: ...ages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon Bus start failure 01 None Negative power fault 1A None Bus over 02 None Battery SCR short circuited...

Page 23: ...ing twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beepi...

Page 24: ...oads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then U...

Page 25: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 26: ...2 A 10 max Charging Voltage 13 65 V 1 Long run Model Type Depending on applications Numbers 16 20 Charging Current 4 A 10 max 4 A 10 max Charging Voltage 13 65 V 1 PHYSICAL Standard Model Dimension DX...

Page 27: ...25...

Reviews: