3)    Make  sure  the  battery  numbers  setting  on  the  control  board  (Please  refer  to  the  section  3-4-12  for 

detailed setting) is consistent to real connection. 

5. Battery mode operation 

1)    When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. If the 

battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery voltage 

drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that the battery 

is at low level and the UPS will shut down automatically soon. Users could switch off some non-critical 

loads  to  disable  the  shutdown  alarm  and  prolong  the  backup  time  (the  UPS  would  cut  off  the 

programmable  output  terminal  automatically  when  the  programmable  timer  function  is  enabled).  If 

there  is  no  more  load  to  be  switched  off  at  that  time,  you  have  to  shut  down  all  loads  as  soon  as 

possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.   

2)    In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer. 

3)    The backup time of the long-run model depends on the external battery capacity. 

4)    The backup time may vary from different environment temperature and load type. 

5)    When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5 hours, 

UPS  will  shut  down  automatically  to  protect  the  battery.  This  battery  discharge  protection  can  be 

enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section) 

6. Test the batteries 

1)    If you need to check the battery status when the UPS is running in AC mode/CVCF mode/ECO mode, 

you could press the 

“Test” button to let the UPS do battery self-test. 

2)    To keep the system reliable, the UPS will perform the battery self-test automatically periodically. The 

default setting period is once per week. 

3)    Users also can set battery self-test through monitoring software. 

4)    If the UPS is at battery self-test, the LCD display and buzzer indication will be the same as at Battery 

mode except that the battery LED is flashing. 

7. Turn off the UPS with utility power supply in AC mode 

1)    Turn off the inverter  of the UPS  by pressing 

“OFF” button for at least 0.5s, and then the buzzer will 

beep once. The UPS will turn into Bypass mode.

   

NOTE 1: 

If the UPS has been set to enable the bypass output, it will bypass voltage from utility power 

to output sockets and terminal even though you have turned off the UPS (inverter). 

NOTE 2:

 After turning off the UPS, please be aware that the UPS is working at Bypass mode and there 

is risk of power loss for connected devices.   

2)    In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the 

input  breaker.  A  few  seconds  later,  there  is  no  display  shown  on  the  display  panel  and  UPS  is 

complete off. 

8. Turn off the UPS without utility power supply in Battery mode 

1)    Turn off the UPS by pressing 

“OFF” button for at least 0.5s, and then the buzzer will beep once. 

2)    Then UPS will cut off power to output and there is no display shown on the display panel. 

9. Mute the buzzer 

1)    To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the 

Summary of Contents for Adapt BX 10K

Page 1: ...Single Phase Online UPS Liebert Adapt BX User Manual 6k 10kVA...

Page 2: ...4 UPS Installation for Parallel System 6 2 5 Software Installation 6 3 Operations 7 3 1 Button Operation 7 3 2 LED Indicators and LCD Panel 7 3 3 Audible Alarm 9 3 4 Single UPS Operation 10 3 5 Parall...

Page 3: ...for ventilation UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualifie...

Page 4: ...000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 3 Low Frequency Signals IEC EN 61000 2 2 W...

Page 5: ...lug One parallel cable only available for parallel model One share current cable only available for parallel model NOTE Before installation please inspect the unit Be sure that nothing inside the pack...

Page 6: ...as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all...

Page 7: ...ry The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for long run model Make sure a DC breaker or other prote...

Page 8: ...g to the section 2 3 2 Connect the output wires of each UPS to an output breaker 3 Connect all output breakers to a major output breaker Then this major output breaker will directly connect to the loa...

Page 9: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press t...

Page 10: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 11: ...lt mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO enable Fan failure Over temperature Charger failur...

Page 12: ...rned on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel...

Page 13: ...7 LCD setting section 6 Test the batteries 1 If you need to check the battery status when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery se...

Page 14: ...t off you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the input breaker and switch off the battery breaker...

Page 15: ...the parallel models and follow the wiring refer to section 2 3 3 Install the new parallel system refers to the previous section 3 Remove one unit from the parallel system 1 If the bypass is abnormal...

Page 16: ...B Subtract ADD Add ON On OFF Off FBD Not allowed OPN Allow RES Reserved 3 7 LCD Setting There are three parameters to set up the UPS Refer to following diagram Parameter 1 It s for program alternative...

Page 17: ...tput voltage in parameter 3 208 Presents output voltage is 208Vac 220 Presents output voltage is 220Vac 230 Presents output voltage is 230Vac 240 Presents output voltage is 240Vac 02 Output frequency...

Page 18: ...e default value is 110V Parameter 3 Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V 04 Frequency range for bypass Interface Setting Paramete...

Page 19: ...Hz 08 Bypass mode setting Interface Setting Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected i...

Page 20: ...battery 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage range is from 0V to 5 7V the default va...

Page 21: ...output for energy saving LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery...

Page 22: ...ages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon Bus start failure 01 None Negative power fault 1A None Bus over 02 None Battery SCR short circuited...

Page 23: ...ing twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beepi...

Page 24: ...oads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then U...

Page 25: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 26: ...2 A 10 max Charging Voltage 13 65 V 1 Long run Model Type Depending on applications Numbers 16 20 Charging Current 4 A 10 max 4 A 10 max Charging Voltage 13 65 V 1 PHYSICAL Standard Model Dimension DX...

Page 27: ...25...

Reviews: