13
SRH 004--016 -- R 407C
Size
004
204
006
206
007
207
008
011
014
016
Power supply
---
400 V / 3 Ph / 50 Hz
OA
(1)
FLA
LRA
Compressors power input
(1)
Compressors nominal current
(1)
Compressor max. current
Fans power input
A
A
A
kW
A
A
kW
32
43
183
13.4
24
35
3.2
32
46
125
13.4
24
19
3.2
41
58
223
19.8
33
50
3.8
42
66
167
19.4
34
29
3.8
49
77
278
24.8
41
69
3.3
50
72
185
25.0
42
32
3.3
64
86
226
26.7
48
35
6.5
82
116
281
39.6
66
50
7.6
101
163
364
44.5
76
69
11.4
125
169
417
60.8
100
72
11.4
Fans max. power input
Fans max. current
kW
A
4.9
8.2
SHC std. head pressure pump model (Opt.)
FHE std. head pressure pump model (Opt.)
Std. head pressure pump motor nom. power
Std. head pressure pump motor max. power
Std. head pressure pump max. current
SHC high head pressure pump model (Opt.)
High head pressure pump motor nom. power
High head pressure pump motor max. power
High head pressure pump max. current
---
---
kW
kW
A
---
kW
A
12 --- 136
---
1.1
1.44
2.67
32---160/30
3.0
6.50
20 --- 128
---
1.5
1.92
3.90
32 --- 160/30
3.0
6.50
20 --- 134
---
1.85
2.45
4.61
40---160/40
4.0
8.50
---
40---160/40
4.0
4.0
8.50
40---200/75
7.5
15.50
Electrical cable section (min.)
mm
2
16
16
25
25
35
35
35
50
70
95
(1) Outdoor air temperature 35
û
C; 30% glycol water mixture; water inlet/outlet temperature 15/10
û
C.
Nominal air flow and 50 Pa available air static pressure.
SRH 017--032 -- R 407C
Size
017
020
023
025
028
030
032
Power supply
---
400 V / 3 Ph / 50 Hz
OA
(1)
FLA
LRA
Compressors power input
(1)
Compressors nominal current
(1)
Compressor max. current
Fans power input
A
A
A
kW
A
A
kW
127
165
305
58.5
102
35
10.8
137
195
360
66.5
112
50
10.8
165
233
398
79.7
132
50
14.6
185
271
472
92.5
152
69
14.6
203
317
518
96.9
162
69
18.3
229
323
571
114.8
188
72
18.3
249
329
577
128.1
208
72
20.3
Fans max. power input
Fans max. current
kW
A
4.9
8.2
Std. head pressure pump model (Opt.)
Std. head pressure pump motor power
Std. head pressure pump max. current
High head pressure pump model (Opt.)
High head pressure pump motor power
High head pressure pump max. current
---
kW
A
---
kW
A
65 --- 260/2
4.0
8.00
65 --- 340/2
5.5
11.20
65 --- 340/2
5.5
11.20
65 --- 410/2
7.5
15.20
65 --- 410/2
7.5
15.20
65 --- 460/2
11.0
21.40
Electrical cable section (min.)
mm
2
70
95
120
150
185
185
185
(1) Outdoor air temperature 35
û
C; 30% glycol water mixture; water inlet/outlet temperature 15/10
û
C.
Nominal air flow and 50 Pa available air static pressure.
•
Nominal power supply = 400 V; 3 Ph; 50 Hz
•
Nominal power supply tolerance = 400 V ±10 %
•
Max. voltage unbalance = 3 %
•
The cables have to be sized in compliance with local standards and according to the type and characteristics of installation. Suggested cables section are
referred to PVC insulation with a max. working temperature of 70
û
C and an ambient temperature of 30
û
C.