SL-23188_REV1_08-10
1
Guide Specifications
Liebert
®
GXT3
™
5000 & 6000VA RT208 Rack-Tower models, Dual Inverter
GUIDE SPECIFICATIONS
1.0 GENERAL
1.1
SUMMARY
This specification shall define the electrical and mechanical characteristics and requirements for a continuous-
duty, single-phase, solid-state uninterruptible power system (UPS). The UPS shall provide high-quality AC power
for sensitive, electronic equipment loads. The UPS is not designed to support large inductive or half-wave
rectified loads, for example: motors, compressors, vacuum pumps, electric drills, laser printers and hair dryers.
1.2
STANDARDS
The UPS shall be designed in accordance with applicable sections of the current revision of the following
documents. Where a conflict arises between these documents and statements made herein, the statements in this
specification shall govern.
208V Nominal Units
UL Standard 1778, c-UL
CSA 22.2 No. 107.1
NEMA Type 1 Enclosure
FCC Part 15, Class A
CISPR22 Class A (RFI)
IEC 61000-3-12 (Harmonics)
IEC/EN/AS 62040-2 2nd Ed (Cat 2 - Table 6):
EN61000-4-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN61000-4-5, Level 3, Criteria A
EN61000-4-6
ANSI C62.41, Category A
EN61000-4-5, Level 3, Criteria A
RoHS (6 by 6)
ISTA Procedure 1A