Guide Specifications 

2.4 

BYPASS 

2.4.1  General 

A bypass circuit shall be provided as an integral part of the UPS. The bypass shall have a make-before-break 
transfer, shall have a maximum detect and transfer time of 4-6 milliseconds and shall be a double-pole device. 
The bypass circuit shall be designed to ensure the simultaneous transfer of the L1 and L2 poles. The bypass shall 
be configured to wrap around the PFC converter, battery charger, DC-DC converter, inverter and battery. The 
bypass circuit shall use the rear-panel mounted UPS input circuit breaker and route bypass power through the 
UPS input filters and surge suppression circuit. The bypass circuit default position shall be in the Bypass mode 
(utility). 

2.4.2  Automatic Transfers 

The transfer control logic shall activate the bypass automatically, transferring the critical AC load to the bypass 
source, after the transfer logic senses one of the following conditions: 

 

UPS overload 

 

UPS overtemperature 

 

PFC failure 

 

Inverter failure 

 

DC bus overvoltage 

Once the overload condition is reduced, the load shall be automatically transferred back to inverter power. An 
overtemperature requires manual transfer back to inverter power after cooling. 

2.5 

INTERNAL BATTERY 

Valve-regulated, non-spillable, lead acid cells shall be used as a stored-energy source for the specified UPS 
system. The battery kit shall be internal to the UPS cabinet and sized to support the inverter at rated load and 
power factor with an ambient temperature of 77°F (25°C) for a minimum of 5 minutes reserve time. The expected 
life of the battery shall be 3-5 years or a minimum 250 complete discharge cycles at ambient temperature of 77°F 
(25°C). To promote battery service life and eliminate over-discharge of the battery, the end-of-discharge DC 
shutdown voltage shall be automatically adjusted by the microprocessor based upon the percentage load at the 
onset of battery operation. 

2.6 

OUTPUT DISTRIBUTION 

Output distribution shall be integral to the UPS cabinet and located on the rear of the unit. The output distribution 
shall provide the capability to re-configure the UPS input and output connections via a removable sheet metal 
power distribution box. Distribution options shall be available with break-before-make maintenance bypass 
switch to allow for complete shutdown and isolation of the UPS for service without powering down the 
connected loads. Maximum transfer time of the maintenance bypass switch shall be 4-6ms. Standard output 
distribution configurations shall be: 

Distribution 

Model 

Utility Input 
Connection 

Output Load Connections 

Maintenance 

Bypass 

PD2-HDWR 

Hardwire Terminals,  
3-wire-plus-ground, 8AWG max 

Hardwire Terminals,  
3-wire plus Ground, 8AWG max 

None 

PD2-HDWR-MBS 

Hardwire Terminals,  
3-wire-plus-ground, 8AWG max 

Hardwire Terminals,  
3-wire plus Ground, 8AWG max 

Included 

PD2-001 

NEMA L14-30P 

NEMA L6-30R, (1) NEMA L14-30R, 
(4) 5-20R (T-Slot) 

Included 

PD2-002 

NEMA L14-30P 

NEMA L6-20R, 
(2) 5-20R (T-Slot) 

Included 

PD2-003 

NEMA L14-30P 

(2) NEMA L6-30R, 
(4) 5-20R (T-Slot) 

Included 

PD2-004 

NEMA L14-30P 

(4) 5-20R (T-Slot), (2) L5-30R 

Included 

PD2-005 

NEMA L14-30P 

(4) L5-20R, (2) L6-30R 

Included 

Summary of Contents for GXT3 5000RT208

Page 1: ...vacuum pumps electric drills laser printers and hair dryers 1 2 STANDARDS The UPS shall be designed in accordance with applicable sections of the current revision of the following documents Where a c...

Page 2: ...DC converter to the inverter to generate computer grade power for the connected load C Recharge When the UPS is supplied with qualified utility power the UPS shall charge connected internal and optio...

Page 3: ...is started on battery with no input power present the default output voltage shall be 120 208V 60Hz from the factory After the UPS has been started from utility the output voltage frequency shall matc...

Page 4: ...all auto sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency Once started the input frequency operating window shall be 40 70Hz wit...

Page 5: ...B Voltage Regulation L1 N and L2 N 3 steady state L1 L2 5 steady state C Frequency Regulation 3 5Hz synchronized to utility mains 0 1Hz free running or on battery operation D Frequency Slew Rate 1 0H...

Page 6: ...harge compliant to EN61000 4 2 level 4 Criteria A without damage and shall not affect the connected load 1 5 USER DOCUMENTATION The specified UPS system shall be supplied with a Safety Warning Sheet T...

Page 7: ...llable lead acid cells housed in a separate cabinet that matches the UPS cabinet styling The cabinet shall be cleaned primed and painted Black RAL 7021 The external battery system shall be sized to pr...

Page 8: ...ritical load shall be transferred to internal bypass 2 2 2 Inverters 2 2 2 1 General The UPS inverters shall be of a pulse width modulated PWM IGBT design capable of providing the specified AC output...

Page 9: ...ostics AC Input indicator 1 green LED The AC Input indicator LED shall be illuminated when utility power is available and falls within the input specification UPS ON indicator 1 green LED The On Inver...

Page 10: ...ed load and power factor with an ambient temperature of 77 F 25 C for a minimum of 5 minutes reserve time The expected life of the battery shall be 3 5 years or a minimum 250 complete discharge cycles...

Page 11: ...Liebert GXT3 5000 6000RT208 SL 23188_REV1_08 10 11 Guide Specifications PD2 006 NEMA L14 30P 4 L6 20R Included...

Page 12: ...SLOT COMMUNICATION OPTIONS The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field install optional Liebert IntelliSlot communication cards Liebert IntelliSlot...

Page 13: ...put voltages to match input voltages of 200 100 220 110 220 127 230 115 or 240 120 Enable Disable Auto Restart Select frequency converter operation with a fixed output frequency of 50 or 60Hz Bypass i...

Reviews: