Liebert GXT3-5000/6000RT208 

 
SL-23188_REV1_08-10 

12 

Guide Specifications 

2.7 

ON-BOARD COMMUNICATION 

The Liebert GXT3 shall offer multiple communication options such as: 

A.

 

USB:

 All models shall work with the Power Management system in Microsoft

®

 Windows

®

 2000, Windows 

XP, Windows Vista

®

, Linux and Mac OS

®

 X. 

B.

 

Remote Emergency Power Off (REPO):

 The UPS shall be equipped with rear-panel terminal connections 

for interface with either a normally open (N.O.) or normally closed (N.C.) field-supplied switch. The remote 
emergency power off function shall allow the user to disable all UPS outputs in an emergency situation. 
Connections must not exceed NEC Class 2 limits. Activation of the REPO circuit shall disable the UPS until 
the following occurs: 

 

REPO contacts are reset. 

 

User restart of the UPS using the front control panel. 

C.

 

Terminal Block Communication:

 includes 8 pins 

Pin 

Definition 

1 & 2 

 Low Battery Warning  

3 & 4 

 On Battery Warning  

5 & 6 

 Any Mode Shutdown  

7 & 8 

 Battery Mode Shutdown  

D.

 

Liebert IntelliSlot

®

 Port 

Simultaneous communication shall be available via terminal block (EPO), USB and Liebert IntelliSlot. 

2.8 

LIEBERT INTELLISLOT COMMUNICATION OPTIONS 

The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field-install optional 
Liebert IntelliSlot communication cards. Liebert IntelliSlot cards may be installed during any state of UPS 
operation (On, Standby or Off states). Available Liebert IntelliSlot options are described below. 

Liebert IntelliSlot Web Card (IS-WEBCARD) 

The optional Liebert IntelliSlot Web Card shall deliver SNMP and Web management to the UPS when 
connected to any 10 or 100 Mbit Ethernet network. The card shall support 10 and 100 Mbit Ethernet and 
shall provide for in-the-field upgrade of SNMP firmware. The kit shall include the Liebert IntelliSlot card, 
MIB, configuration cable and user manual. Once the card is installed, serial communication shall be disabled 
in the DB9F connector; however, the photo-coupler signals (On Battery and Low Battery) shall remain 
active. 

Liebert IntelliSlot Relay Interface Card (RELAYCARD-INT) 

The optional Liebert IntelliSlot Relay Interface Card shall provide contact closure for remote monitoring of 
alarm conditions in the UPS, delivering signals for On Battery, On Bypass, Low Battery, Summary Alarm, 
UPS Fault and On UPS. The contacts shall be rated for 24VAC or 24VDC at 1A. Connection shall be to a 
DB25F connector with cable provided by the end user. 
 

Summary of Contents for GXT3 5000RT208

Page 1: ...vacuum pumps electric drills laser printers and hair dryers 1 2 STANDARDS The UPS shall be designed in accordance with applicable sections of the current revision of the following documents Where a c...

Page 2: ...DC converter to the inverter to generate computer grade power for the connected load C Recharge When the UPS is supplied with qualified utility power the UPS shall charge connected internal and optio...

Page 3: ...is started on battery with no input power present the default output voltage shall be 120 208V 60Hz from the factory After the UPS has been started from utility the output voltage frequency shall matc...

Page 4: ...all auto sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency Once started the input frequency operating window shall be 40 70Hz wit...

Page 5: ...B Voltage Regulation L1 N and L2 N 3 steady state L1 L2 5 steady state C Frequency Regulation 3 5Hz synchronized to utility mains 0 1Hz free running or on battery operation D Frequency Slew Rate 1 0H...

Page 6: ...harge compliant to EN61000 4 2 level 4 Criteria A without damage and shall not affect the connected load 1 5 USER DOCUMENTATION The specified UPS system shall be supplied with a Safety Warning Sheet T...

Page 7: ...llable lead acid cells housed in a separate cabinet that matches the UPS cabinet styling The cabinet shall be cleaned primed and painted Black RAL 7021 The external battery system shall be sized to pr...

Page 8: ...ritical load shall be transferred to internal bypass 2 2 2 Inverters 2 2 2 1 General The UPS inverters shall be of a pulse width modulated PWM IGBT design capable of providing the specified AC output...

Page 9: ...ostics AC Input indicator 1 green LED The AC Input indicator LED shall be illuminated when utility power is available and falls within the input specification UPS ON indicator 1 green LED The On Inver...

Page 10: ...ed load and power factor with an ambient temperature of 77 F 25 C for a minimum of 5 minutes reserve time The expected life of the battery shall be 3 5 years or a minimum 250 complete discharge cycles...

Page 11: ...Liebert GXT3 5000 6000RT208 SL 23188_REV1_08 10 11 Guide Specifications PD2 006 NEMA L14 30P 4 L6 20R Included...

Page 12: ...SLOT COMMUNICATION OPTIONS The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field install optional Liebert IntelliSlot communication cards Liebert IntelliSlot...

Page 13: ...put voltages to match input voltages of 200 100 220 110 220 127 230 115 or 240 120 Enable Disable Auto Restart Select frequency converter operation with a fixed output frequency of 50 or 60Hz Bypass i...

Reviews: