Liebert GXT3-5000/6000RT208 

 
SL-23188_REV1_08-10 

Guide Specifications 

1.3.3  Performance Requirements 

1.3.3.1  AC Input to UPS 

A.

 

Voltage:

 The point at which the UPS transfers to battery operation shall be dependent on the amount of load 

that the UPS is supporting. The UPS shall operate from the following voltage ranges without drawing power 
from the batteries: 

Low Line Voltage Range 

Low Line Voltage 

GXT3-5000RT208 

GXT3-6000RT208 

100% to 91% 

L/L Transfer 

88 ± 3.1VAC 

98 ± 3.1VAC 

L/L Comeback 

95 ± 3.1VAC 

105 ± 3.1VAC 

90% to 71% 

L/L Transfer 

84 ± 3.1VAC 

88 ± 3.1VAC 

L/L Comeback 

91 ± 3.1VAC 

95 ± 3.1VAC 

70% to 31% 

L/L Transfer 

70 ± 3.1VAC 

74 ± 3.1VAC 

L/L Comeback 

77 ± 3.1VAC 

81 ± 3.1VAC 

30% to 0% 

L/L Transfer 

60 ± 3.1VAC 

60 ± 3.1VAC 

L/L Comeback 

67 ± 3.1VAC 

67 ± 3.1VAC 

High Line Voltage Range 

High Line Voltage 

208V Models 

High Line Transfer 

139.5 ± 3.1VAC 

High Line Comeback 

132.5 ± 3.1VAC 

B.

 

Frequency:

 The UPS shall auto-sense input frequency of 50Hz or 60Hz when first powered up and shall use 

this frequency as the default output frequency. Once started the input frequency operating window shall be 
40-70Hz without going to batteries. The UPS shall be capable of cold start with a default output frequency of 
60Hz. 

C.

 

Input Power Factor:

 >0.99 lagging at rated load. 

D.

 

Input Current reflected distortion:

 5% THD maximum at rated load. 

E.

 

Input Current Ratings: 

UPS Model # 

VA 

Watt 

Hz 

VAC 

L1 

L2 

Total Amps 

GXT3-5000RT208 

5000 

4000 

50/60 

120/240 

10.4 

10.4 

20.8 

5000 

4000 

50/60 

115/230 

10.85 

10.85 

21.7 

5000 

4000 

50/60 

120/208 

10.4 

10.4 

20.8 

4500 

3600 

50/60 

110/220 

10.25 

10.25 

20.5 

4000 

3200 

50/60 

100/200 

10 

10 

20 

GXT3-6000RT208 

6000 

4800 

50/60 

120/240 

12.5 

12.5 

25 

5600 

4800 

50/60 

115/230 

12.15 

12.15 

24.3 

6000 

4800 

50/60 

120/208 

12.5 

12.5 

25 

5400 

4320 

50/60 

110/220 

12.25 

12.25 

24.5 

3840 

4800 

50/60 

100/200 

12 

12 

24 

F.

 

Surge Protection:

 The UPS shall utilize metal oxide varistors (MOVs) rated at 175V, 150 Joules minimum 

connected L1-N and L2-N; 300V, 150 Joules minimum connected L1-G, L2-G and N-G. 

 

Summary of Contents for GXT3 5000RT208

Page 1: ...vacuum pumps electric drills laser printers and hair dryers 1 2 STANDARDS The UPS shall be designed in accordance with applicable sections of the current revision of the following documents Where a c...

Page 2: ...DC converter to the inverter to generate computer grade power for the connected load C Recharge When the UPS is supplied with qualified utility power the UPS shall charge connected internal and optio...

Page 3: ...is started on battery with no input power present the default output voltage shall be 120 208V 60Hz from the factory After the UPS has been started from utility the output voltage frequency shall matc...

Page 4: ...all auto sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency Once started the input frequency operating window shall be 40 70Hz wit...

Page 5: ...B Voltage Regulation L1 N and L2 N 3 steady state L1 L2 5 steady state C Frequency Regulation 3 5Hz synchronized to utility mains 0 1Hz free running or on battery operation D Frequency Slew Rate 1 0H...

Page 6: ...harge compliant to EN61000 4 2 level 4 Criteria A without damage and shall not affect the connected load 1 5 USER DOCUMENTATION The specified UPS system shall be supplied with a Safety Warning Sheet T...

Page 7: ...llable lead acid cells housed in a separate cabinet that matches the UPS cabinet styling The cabinet shall be cleaned primed and painted Black RAL 7021 The external battery system shall be sized to pr...

Page 8: ...ritical load shall be transferred to internal bypass 2 2 2 Inverters 2 2 2 1 General The UPS inverters shall be of a pulse width modulated PWM IGBT design capable of providing the specified AC output...

Page 9: ...ostics AC Input indicator 1 green LED The AC Input indicator LED shall be illuminated when utility power is available and falls within the input specification UPS ON indicator 1 green LED The On Inver...

Page 10: ...ed load and power factor with an ambient temperature of 77 F 25 C for a minimum of 5 minutes reserve time The expected life of the battery shall be 3 5 years or a minimum 250 complete discharge cycles...

Page 11: ...Liebert GXT3 5000 6000RT208 SL 23188_REV1_08 10 11 Guide Specifications PD2 006 NEMA L14 30P 4 L6 20R Included...

Page 12: ...SLOT COMMUNICATION OPTIONS The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field install optional Liebert IntelliSlot communication cards Liebert IntelliSlot...

Page 13: ...put voltages to match input voltages of 200 100 220 110 220 127 230 115 or 240 120 Enable Disable Auto Restart Select frequency converter operation with a fixed output frequency of 50 or 60Hz Bypass i...

Reviews: