background image

 

 

Liebert GXT3-5000/6000RT208 

 
SL-23188_REV1_08-10 

Guide Specifications 

1.3.3.2  AC Output, UPS Inverters 

A.

 

Voltage Configuration:

 50/60Hz, single-phase, 3-wire-plus-ground. 

Default setting 120/208V. Output L-N voltage shall be selectable via the included UPS configuration 
program. Optional settings shall be 100/200V, 110/220V, 115/230V, 120/208V, 120/240V or 127/220V. The 
UPS shall adjust sinewave amplitude and/or phase-angle relationship of the inverters to produce the selected 
voltage to match the input.  

Note

: At 100/200V setting, the UPS shall be derated to 80% of the rated 120/208V capacity; at 110/220V, the 

UPS shall be derated to 90% of the rated 120/208V capacity. 

B.

 

Voltage Regulation:

 

L1-N and L2-N: ±3% steady state. 

 

 

 

 

 

L1-L2: ±5% steady state. 

C.

 

Frequency Regulation:

  ±3.5Hz synchronized to utility / mains. 

 

 

 

 

 

±0.1Hz free running or on battery operation. 

D.

 

Frequency Slew Rate:

 1.0Hz per second maximum 

E.

 

Load Power Factor Range:

 0.65 lagging to 1.0 (unity) 

F.

 

Voltage Distortion: 

Sinusoidal Waveform; ≤3% total harmonic distortion (THD) into a 100% linear load; 

≤5% THD into a 100% non-linear load with a crest factor ratio of 3:1. 

G.

 

Inverter Overload Capability: 

Overload Percent 

Duration Inverter shall support rated load 

105% to 130% 

1 minute 

131% to 150% 

10 seconds 

151% to 200% 

1 second 

>200% (impact load) 

At least 5 cycles 

H.

 

Voltage Transient Response:

 ±7% on-line or Battery mode for 0-100-0 % loading of the UPS, ±4% on-line 

or Battery mode for 20-100-20 % loading of the UPS. 

I.

 

Transient Recovery Time:

 To nominal voltage within 166 milliseconds. 

J.

 

Efficiency:

 91% AC-AC 

Summary of Contents for GXT3 5000RT208

Page 1: ...vacuum pumps electric drills laser printers and hair dryers 1 2 STANDARDS The UPS shall be designed in accordance with applicable sections of the current revision of the following documents Where a c...

Page 2: ...DC converter to the inverter to generate computer grade power for the connected load C Recharge When the UPS is supplied with qualified utility power the UPS shall charge connected internal and optio...

Page 3: ...is started on battery with no input power present the default output voltage shall be 120 208V 60Hz from the factory After the UPS has been started from utility the output voltage frequency shall matc...

Page 4: ...all auto sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency Once started the input frequency operating window shall be 40 70Hz wit...

Page 5: ...B Voltage Regulation L1 N and L2 N 3 steady state L1 L2 5 steady state C Frequency Regulation 3 5Hz synchronized to utility mains 0 1Hz free running or on battery operation D Frequency Slew Rate 1 0H...

Page 6: ...harge compliant to EN61000 4 2 level 4 Criteria A without damage and shall not affect the connected load 1 5 USER DOCUMENTATION The specified UPS system shall be supplied with a Safety Warning Sheet T...

Page 7: ...llable lead acid cells housed in a separate cabinet that matches the UPS cabinet styling The cabinet shall be cleaned primed and painted Black RAL 7021 The external battery system shall be sized to pr...

Page 8: ...ritical load shall be transferred to internal bypass 2 2 2 Inverters 2 2 2 1 General The UPS inverters shall be of a pulse width modulated PWM IGBT design capable of providing the specified AC output...

Page 9: ...ostics AC Input indicator 1 green LED The AC Input indicator LED shall be illuminated when utility power is available and falls within the input specification UPS ON indicator 1 green LED The On Inver...

Page 10: ...ed load and power factor with an ambient temperature of 77 F 25 C for a minimum of 5 minutes reserve time The expected life of the battery shall be 3 5 years or a minimum 250 complete discharge cycles...

Page 11: ...Liebert GXT3 5000 6000RT208 SL 23188_REV1_08 10 11 Guide Specifications PD2 006 NEMA L14 30P 4 L6 20R Included...

Page 12: ...SLOT COMMUNICATION OPTIONS The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field install optional Liebert IntelliSlot communication cards Liebert IntelliSlot...

Page 13: ...put voltages to match input voltages of 200 100 220 110 220 127 230 115 or 240 120 Enable Disable Auto Restart Select frequency converter operation with a fixed output frequency of 50 or 60Hz Bypass i...

Reviews: