Liebert GXT3-5000/6000RT208
SL-23188_REV1_08-10
5
Guide Specifications
1.3.3.2 AC Output, UPS Inverters
A.
Voltage Configuration:
50/60Hz, single-phase, 3-wire-plus-ground.
Default setting 120/208V. Output L-N voltage shall be selectable via the included UPS configuration
program. Optional settings shall be 100/200V, 110/220V, 115/230V, 120/208V, 120/240V or 127/220V. The
UPS shall adjust sinewave amplitude and/or phase-angle relationship of the inverters to produce the selected
voltage to match the input.
Note
: At 100/200V setting, the UPS shall be derated to 80% of the rated 120/208V capacity; at 110/220V, the
UPS shall be derated to 90% of the rated 120/208V capacity.
B.
Voltage Regulation:
L1-N and L2-N: ±3% steady state.
L1-L2: ±5% steady state.
C.
Frequency Regulation:
±3.5Hz synchronized to utility / mains.
±0.1Hz free running or on battery operation.
D.
Frequency Slew Rate:
1.0Hz per second maximum
E.
Load Power Factor Range:
0.65 lagging to 1.0 (unity)
F.
Voltage Distortion:
Sinusoidal Waveform; ≤3% total harmonic distortion (THD) into a 100% linear load;
≤5% THD into a 100% non-linear load with a crest factor ratio of 3:1.
G.
Inverter Overload Capability:
Overload Percent
Duration Inverter shall support rated load
105% to 130%
1 minute
131% to 150%
10 seconds
151% to 200%
1 second
>200% (impact load)
At least 5 cycles
H.
Voltage Transient Response:
±7% on-line or Battery mode for 0-100-0 % loading of the UPS, ±4% on-line
or Battery mode for 20-100-20 % loading of the UPS.
I.
Transient Recovery Time:
To nominal voltage within 166 milliseconds.
J.
Efficiency:
91% AC-AC