Liebert GXT3-5000/6000RT208 

 
SL-23188_REV1_08-10 

Guide Specifications 

2.0 PRODUCT 

2.1 

FABRICATION 

All materials and components making up the UPS shall be new, of current manufacture and shall not have been in 
prior service except as required during factory testing. All relays shall be provided with dust covers. 

2.1.1  Wiring 

Wiring practices, materials and coding shall be in accordance with the requirements the standards listed in 
Section 1.2 and other applicable codes and standards. All wiring shall be copper. 

2.1.2  Cabinet 

The UPS unit shall be composed of: input PFC converter, battery charger, dual-inverter, input filter and internal 
bypass circuit; and batteries consisting of the appropriate number of sealed battery cells; and shall be housed in a 
rack-tower NEMA type 1 enclosure and shall meet the requirements of IP20. The UPS cabinet shall be cleaned, 
primed and painted RAL 7021 Black. The internal battery unit shall be shipped separately and shall be installed 
during the UPS installation process. 

2.1.3  Matching Battery Cabinets 

The optional Rack-Tower battery cabinet shall contain valve-regulated, non-spillable, lead acid cells, housed in a 
separate cabinet that matches the UPS cabinet styling. The cabinet shall be cleaned, primed and painted Black 
RAL 7021. The external battery system shall be sized to provide an additional 9-11 minutes of reserve power at 
rated load. The matching battery cabinet shall include an 18" (0.45m) detachable, molded interconnect cable, 
circuit breaker overcurrent protection and provisions for daisy-chain connection of additional battery cabinets. 

The model numbers, dimensions and weight information of the UPS cabinet and optional external battery cabinet 
shall be as follows: 

Model 

Rack Dimensions 

W x D x H, in. (mm) 

Tower Dimensions 

W x D x H, in. (mm) 

Weight 
lb. (kg) 

GXT3-5000RT208 

16.9 x 26.1 x 6.8 

(430 x 662 x 173) 

6.8 x 26.1 x 16.9 

(173 x 662 x 430) 

132 (59.9)* 

GXT3-6000RT208 

16.9 x 26.1 x 6.8 

(430 x 662 x 173) 

6.8 x 26.1 x 16.9 

(173 x 662 x 430) 

132 (59.9)* 

GXT3-144VBATT 

(Optional External Battery) 

16.9 x 26.1 x 3.3 

(430 x 662 x 85) 

3.3 x 26.1 x 16.9 

(85 x 662 x 430) 

99.9 (45.3)* 

* Specified weights include the standard internal battery kit (1), Part Number GXT3-144BATKIT. 

2.1.4  Cooling 

The UPS shall be forced air cooled by internally mounted, continuous fans. Fan power shall be provided from the 
internal DC supply. Air intake shall be through the front of the unit, and air exhaust shall be out the rear of the 
unit. 

Summary of Contents for GXT3 5000RT208

Page 1: ...vacuum pumps electric drills laser printers and hair dryers 1 2 STANDARDS The UPS shall be designed in accordance with applicable sections of the current revision of the following documents Where a c...

Page 2: ...DC converter to the inverter to generate computer grade power for the connected load C Recharge When the UPS is supplied with qualified utility power the UPS shall charge connected internal and optio...

Page 3: ...is started on battery with no input power present the default output voltage shall be 120 208V 60Hz from the factory After the UPS has been started from utility the output voltage frequency shall matc...

Page 4: ...all auto sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency Once started the input frequency operating window shall be 40 70Hz wit...

Page 5: ...B Voltage Regulation L1 N and L2 N 3 steady state L1 L2 5 steady state C Frequency Regulation 3 5Hz synchronized to utility mains 0 1Hz free running or on battery operation D Frequency Slew Rate 1 0H...

Page 6: ...harge compliant to EN61000 4 2 level 4 Criteria A without damage and shall not affect the connected load 1 5 USER DOCUMENTATION The specified UPS system shall be supplied with a Safety Warning Sheet T...

Page 7: ...llable lead acid cells housed in a separate cabinet that matches the UPS cabinet styling The cabinet shall be cleaned primed and painted Black RAL 7021 The external battery system shall be sized to pr...

Page 8: ...ritical load shall be transferred to internal bypass 2 2 2 Inverters 2 2 2 1 General The UPS inverters shall be of a pulse width modulated PWM IGBT design capable of providing the specified AC output...

Page 9: ...ostics AC Input indicator 1 green LED The AC Input indicator LED shall be illuminated when utility power is available and falls within the input specification UPS ON indicator 1 green LED The On Inver...

Page 10: ...ed load and power factor with an ambient temperature of 77 F 25 C for a minimum of 5 minutes reserve time The expected life of the battery shall be 3 5 years or a minimum 250 complete discharge cycles...

Page 11: ...Liebert GXT3 5000 6000RT208 SL 23188_REV1_08 10 11 Guide Specifications PD2 006 NEMA L14 30P 4 L6 20R Included...