Liebert GXT3-5000/6000RT208 

 
SL-23188_REV1_08-10 

Guide Specifications 

2.2.3  Display and Controls 

2.2.3.1  General 

The UPS shall be provided with a microprocessor-based control and a status display section designed for 
convenient and reliable user operation. The monitoring functions such as status and alarm indicators shall be 
displayed on a front-panel LED display. 

2.2.3.2  System Indicators 

The UPS shall include five individual LED status indicators and three rows of LEDs to indicate UPS load and 
battery capacity. An audible alarm shall be used in conjunction with the visual indicators to indicate to the 
operator a change in UPS operating status. 

All audible alarms can be silenced, with the exception of low battery, bypass reminder and missing batteries at 
startup alarms. Once silenced, the audible alarm shall not sound until a new alarm condition is present. Standard 
LED indicators are described below: 

 

Load Level indicators:

 10 total: 4 green and 1 amber, for each of the L1 and L2 outputs. The Load 

Level indicators shall display the approximate load level at all times. 

 

Battery Capacity indicators:

 5 green LEDs. The Battery Capacity LEDs shall display the approximate 

level of battery reserves. 

 

Fault indicator:

 1 red LED. The Fault indicator LED shall illuminate if the UPS detects an internal 

problem. One or more of the Battery Capacity indicators may be illuminated to aid in diagnostics. 

 

AC Input indicator:

 1 green LED. The AC Input indicator LED shall be illuminated when utility power 

is available and falls within the input specification. 

 

UPS ON indicator:

 1 green LED. The On Inverter indicator LED shall be illuminated when the UPS 

inverter is operating and supplying power to connected loads. 

 

On Bypass indicator:

 1 amber LED. The On Bypass indicator LED shall be illuminated when the 

bypass source is supplying power to connected loads. 

 

On Battery indicator:

 1 amber LED. The On Battery indicator LED shall be illuminated when the AC 

Input is out of the acceptable operating range. 

2.2.3.3  On-Standby-Off Controls 

UPS startup and shutdown operations shall be accomplished by the ON and STANDBY push buttons on the front 
panel of the UPS. The ON push button shall be a means to turn the UPS on and shall also serve as a means to 
manually test the battery. The STANDBY push button shall allow manual transfers of the load from the inverter 
to bypass power. Pressing the STANDBY push button in Bypass or Battery mode shall completely shut down the 
UPS and its connected load. 

2.3 

ON-LINE BATTERY TEST 

The UPS shall feature an automatic battery test with the factory default test interval set at every 2 weeks. The 
battery test shall ensure the capability of the battery to supply power to the inverter while loaded. If the battery 
fails the test, the UPS shall display a warning alarm to indicate the internal batteries need replaced and resume 
operation without disturbing the load. The battery test feature shall be user accessible by the push button on the 
front of the unit. 

Summary of Contents for GXT3 5000RT208

Page 1: ...vacuum pumps electric drills laser printers and hair dryers 1 2 STANDARDS The UPS shall be designed in accordance with applicable sections of the current revision of the following documents Where a c...

Page 2: ...DC converter to the inverter to generate computer grade power for the connected load C Recharge When the UPS is supplied with qualified utility power the UPS shall charge connected internal and optio...

Page 3: ...is started on battery with no input power present the default output voltage shall be 120 208V 60Hz from the factory After the UPS has been started from utility the output voltage frequency shall matc...

Page 4: ...all auto sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency Once started the input frequency operating window shall be 40 70Hz wit...

Page 5: ...B Voltage Regulation L1 N and L2 N 3 steady state L1 L2 5 steady state C Frequency Regulation 3 5Hz synchronized to utility mains 0 1Hz free running or on battery operation D Frequency Slew Rate 1 0H...

Page 6: ...harge compliant to EN61000 4 2 level 4 Criteria A without damage and shall not affect the connected load 1 5 USER DOCUMENTATION The specified UPS system shall be supplied with a Safety Warning Sheet T...

Page 7: ...llable lead acid cells housed in a separate cabinet that matches the UPS cabinet styling The cabinet shall be cleaned primed and painted Black RAL 7021 The external battery system shall be sized to pr...

Page 8: ...ritical load shall be transferred to internal bypass 2 2 2 Inverters 2 2 2 1 General The UPS inverters shall be of a pulse width modulated PWM IGBT design capable of providing the specified AC output...

Page 9: ...ostics AC Input indicator 1 green LED The AC Input indicator LED shall be illuminated when utility power is available and falls within the input specification UPS ON indicator 1 green LED The On Inver...

Page 10: ...ed load and power factor with an ambient temperature of 77 F 25 C for a minimum of 5 minutes reserve time The expected life of the battery shall be 3 5 years or a minimum 250 complete discharge cycles...

Page 11: ...Liebert GXT3 5000 6000RT208 SL 23188_REV1_08 10 11 Guide Specifications PD2 006 NEMA L14 30P 4 L6 20R Included...

Page 12: ...SLOT COMMUNICATION OPTIONS The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field install optional Liebert IntelliSlot communication cards Liebert IntelliSlot...

Page 13: ...put voltages to match input voltages of 200 100 220 110 220 127 230 115 or 240 120 Enable Disable Auto Restart Select frequency converter operation with a fixed output frequency of 50 or 60Hz Bypass i...