Operating Range
3 -- 2
Liebert HPC---S 006---022---PD---273571---01.03.2012
Tab. 3a --- Operating range --- Chiller with AC fans 900mm
Models: CB0 006---022
006
007
009
011
014
015
018
019
022
Operating range
Max. outdoor temperature
(1)
°
C
52.0
49.5
54.0
52.5
50.0
48.5
52.0
50.5
49.0
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
4.4
(1) --- With nominal air flow; water outlet temperature 7° C; full load; R410A refrigerant.
Tab. 3b --- Operating range --- Chiller with AC fans 800mm
Models: CB0 006---022
006
007
009
011
014
015
018
019
022
Operating range
Max. outdoor temperature
(1)
°
C
50.0
47.0
52.5
50.5
48.0
46.0
50.0
48.0
46.5
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
4.4
(1) --- With nominal air flow; water outlet temperature 7° C; full load; R410A refrigerant.
Tab. 3c --- Operating range --- Chiller with EC fans 900mm
Models: CG0 006---018
006
007
009
011
014
015
018
Operating range
Max. outdoor temperature
(1)
°
C
53.0
56.0
56.0
53.5
55.5
54.0
53.0
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
5
(1) --- With nominal air flow; water outlet temperature 7° C; full load; R410A refrigerant.
Tab. 3d --- Operating range --- Chiller with EC fans 800mm
Models: CG0 006---018
006
007
009
011
014
015
018
Operating range
Max. outdoor temperature
(1)
°
C
47.0
52.0
51.5
48.0
50.5
48.5
47.0
Safety devices settings
High pressure switch
(1)
High pressure safety valve
HP safety valves (each circuit)
High pressure safety valve connection
Low pressure switch
barg
barg
Nr.
inch
barg
42
45
1
3/4” G
5
(1) --- With nominal air flow; water outlet temperature 7° C; full load; R410A refrigerant.