background image

Refrigerant Circuit

12

12 -- 1

Liebert HPC---S 006---022---PD---273571---01.03.2012

Refrigerant Circuit

14

MC

MC

23

15

18

17

TCE

PZH PZH

2

2

PI

5

PT

11

15

15

15

17

15

PI

PT

TT

10

6

3

TT

26

13

13

16

22

X

12

21

20

PZL

7

1

1

4

4

EVAPORATOR

WATER INLET

EVAPORATOR

WATER OUTLET

Ø E

Ø E

ONLY FOR

MOD. 011--- 022

ONLY ”B”

VERSION

ONLY ”G”

VERSION

ONLY ”G”

VERSION

ONLY ”B”

VERSION

Make tandem compressor

piping following the supplier

assembly instructions.

Ø E

--- Tread coupling.

X

Tab. 12 ---

Refrigerant circuit components --- HPC---S 006---022

(R410A)

Pos.

Description

Pos.

Description

1
2
3
4
5
6
7
8
9

10
11
12
13
14

Compressor
High pressure switch
Transducer pressure sensor

(Low pressure control)

Crankcase heater
High pressure manometer
Low pressure manometer
Low pressure switch

---
---

EEV temperature sensor
Transducer pressure sensor

(High pressure control)

Safety valve
Condenser
Condenser fans

15
16
17
18
19
20
21
22
23
24
25
26
27
28

Service connection
Sight glass
Shut---Off valve
Filter dryer

---

Solenoid valve
Mechanical expansion valve
Electronic expansion valve
Evaporator

---
---

External air temperature sensor

---
---

Summary of Contents for HPC-S 006

Page 1: ...Liebert HPC S 006 022 Air Cooled Chillers with Scroll compressor s Precision Cooling for Business Critical Continuity PRODUCT DOCUMENTATION Liebert HPC S 006 022 PD 273571 01 03 2012...

Page 2: ...f the latest generation specifically designed for air conditioning applications the new series stands out for its unrivalled efficiency outstanding compactness and low sound emissions The Freecooling...

Page 3: ...it The product conforms to European Union directives 2006 42 EC 2004 108 EC 2006 95 EC and 97 23 EC Units are supplied complete with a test certificate and conformity declaration and control component...

Page 4: ...temperature environments as well up to 46 C at 100 full load Resistance to liquid slugging The robust design of the scroll compressors can tolerate withstand amounts of liquid refrigerant that would...

Page 5: ...that even if the outside ambient temperature is not low enough to provide the complete cool ing load a significant contribution to the running costs of the system can be made whenever the ambient tem...

Page 6: ...n System A special working mode can be set up in combination with Emerson Network Power HPAC indoor units to obtain the Supersaver Evolution system that enhances the energy saving capabilities and thu...

Page 7: ...w and control your system via Internet Flexibility Hydronic Module In order tomatch different kinds of installations and ap plications Liebert HPC S 006 022 units are available with a hydronic mod ule...

Page 8: ...and 3 fans Digit 7 Display and Switch A FTE display B FTE display Network Switch E iCOM Coldfire display large F iCOM Coldfire display large Network Switch Digit 8 Soft starter 0 None 1 With compresso...

Page 9: ...le options Rule valid for all Chiller and Freecooling versions Compressor soft starter are not electrically compatible with compressors power factor correc tions D if digit 8 1 than digit 16 0 on digi...

Page 10: ...aximum Outlet Water Temperature of 20 C and Maximum Water Return Temperature of 26 C when the units are at full power The maximum permitted glycol percentage is 50 35 with standard pump groups fitted...

Page 11: ...onnection Low pressure switch barg barg Nr inch barg 42 45 1 3 4 G 4 4 1 With nominal air flow water outlet temperature 7 C full load R410A refrigerant Tab 3c Operating range Chiller with EC fans 900m...

Page 12: ...ection Low pressure switch barg barg Nr inch barg 42 45 1 3 4 G 4 4 1 With nominal air flow mixture outlet temperature 10 C full load R410A refrigerant Tab 3g Operating range Freecooling with EC fans...

Page 13: ...Fans Number of fans No 1 2 3 Type axial Wheel nominal diameter mm 900 RPM 1 min 900 Nominal power input each fan kW 2 4 Fans power input kW 2 4 4 8 7 2 Air flow rate m3 h 21900 21400 44800 43800 4280...

Page 14: ...Number of fans No 1 2 3 Type axial Wheel nominal diameter mm 800 RPM 1 min 900 Nominal power input each fan kW 1 7 Fans power input kW 1 7 3 4 5 1 Air flow rate m3 h 18000 17800 37000 36000 35600 3560...

Page 15: ...with EC motor Wheel nominal diameter mm 900 RPM 1 min 1000 Nominal power input each fan kW 2 6 Fans power input kW 2 6 5 2 7 8 Air flow rate m3 h 23700 50600 48500 47400 72750 72750 71100 Evaporator...

Page 16: ...with EC motor Wheel nominal diameter mm 800 RPM 1 min 718 Nominal power input each fan kW 0 7 Fans power input kW 0 7 1 4 2 1 Air flow rate m3 h 13900 29200 28200 27800 42300 42300 41700 Evaporator Nu...

Page 17: ...input each fan kW 2 4 Fans power input kW 2 4 4 8 7 2 Air flow rate m3 h 19500 41800 39000 58500 Evaporator Number of evaporators No 1 Type brazed plate heat exchanger Internal volume refrigerant side...

Page 18: ...put each fan kW 1 8 Fans power input kW 1 8 3 6 5 4 Air flow rate m3 h 17000 36000 34000 51000 Evaporator Number of evaporators No 1 Type brazed plate heat exchanger Internal volume refrigerant side l...

Page 19: ...ower input kW 2 7 5 4 8 1 Air flow rate m3 h 22000 46600 44000 66000 Evaporator Number of evaporators No 1 Type brazed plate heat exchanger Internal volume refrigerant side l 4 1 5 1 5 6 7 6 9 2 9 2 1...

Page 20: ...er input kW 0 7 1 4 2 1 Air flow rate m3 h 13500 28000 27000 40500 Evaporator Number of evaporators No 1 Type brazed plate heat exchanger Internal volume refrigerant side l 4 1 5 1 5 6 7 6 9 2 9 2 11...

Page 21: ...nd two pressure switches for Mod 011 022 for high pressure and one low pressure safety switch for only Bversion TXV andsolenoid valvefor Bversion and EEV for G version filter dryer with anti acid soli...

Page 22: ...peration of the compressors soas toensure always their operation with in their limits with top reliability the HP and LP alarms the motor thermal protection the start times and the min operation pause...

Page 23: ...ts are made of EPDM This arrangement permits compensation for thermal expansion reduces noise and vibration propagat ing through hydraulic pipelines and facilitates ease of maintenance The anti conden...

Page 24: ...ull out design it is not required to disconnect the pump body from the pipe line due to back pull out design Suction and discharge ports are threaded Rp ISO 7 or flanged according to EN 1092 2 ex UNI...

Page 25: ...It is possible to access the iCOM control display without switching the unit off so as to aid maintenance operations The cooling of the electrical panel is achieved through forced ventilation For low...

Page 26: ...ing to the provisions in the processes procedures and plans for the quality The machine is supplied with a final test certificate and a declaration of conformity with the norms All Liebert HPC S 006 0...

Page 27: ...50 1 85 3 00 Noise Level dB A 63 64 65 66 According to ISO 3744 Tab 5d 2 Pole standard head pressure data referred to each pump Models 006 007 009 011 014 015 018 019 022 FB0 30 glycol water Mixture...

Page 28: ...resis protected D A pad with antislip reliefs stabilizes the damper position by friction They are suitable for dampening high and medium frequency vibrations 10Hz guaranteeing excellent insulation eff...

Page 29: ...e Ambient compensation function can be enabled tomakethe unitset point riseautomatically during warm periods permitting energy savings D For low noise versions with fan speed control there is a specia...

Page 30: ...p every single parameter has its own multi page explana tion D Status Report of the latest 200 event messages of the unit system D Four different Graphic Data Records D Timer and Date mode electronic...

Page 31: ...and compressor power input with 0 ethylene glycol on Chiller models or 30 ethylene glycol on Freecooling models when we use glycol mixtures with different with the same inlet and outlet temperatures...

Page 32: ...und Pressure Levels dB 63 125 250 500 1000 2000 4000 8000 CB0006 FB0006 70 73 73 73 71 65 59 56 75 0 CB0007 FB0007 70 73 73 73 71 65 59 56 75 0 CB0009 FB0009 71 74 74 74 72 66 60 57 76 0 CB0011 FB0011...

Page 33: ...6 83 82 80 76 70 65 84 5 CB0018 FB0018 91 88 85 83 82 77 71 67 86 0 CB0019 FB0019 93 89 85 83 83 77 71 68 86 5 CB0022 FB0022 93 90 85 84 83 78 72 69 87 0 Note Sound power levels tolerance for each oct...

Page 34: ...FG0018 69 62 60 60 58 52 47 41 62 0 Tab 8h PWL CG0 FG0 800EC Models Octave band frequency Hz Total dB A PWL Sound Power Levels dB 63 125 250 500 1000 2000 4000 8000 CG0006 FG0006 82 75 73 73 71 65 60...

Page 35: ...A 370 3 FHE 40 160 30 High head pressure pump Nominal power kW 1 1 1 5 1 85 3 High head pressure pump Max current A 2 5 3 4 4 5 6 3 1 Outdoor temperature 35 C water inlet outlet temperature 12 7 C R41...

Page 36: ...ominal power kW 1 5 1 85 3 4 5 5 High head pressure pump Max current A 3 1 4 2 5 9 6 3 7 7 10 4 1 Outdoor temperature 35 C fluid inlet outlet temperature 15 10 C 70 30 water glycol mixture R410A refri...

Page 37: ...018 019 022 014 015 018 100 100 1180 1440 4000 Tab 10b Weight distribution without tank and pumps Models Size Weight distribution kg Total kg W1 W2 W3 W4 W5 W6 W7 W8 W9 W10 CB0 006 211 156 210 155 732...

Page 38: ...245 241 246 242 974 009 215 215 259 213 213 257 1372 011 242 242 248 258 258 265 1513 014 289 255 255 302 266 266 1633 015 297 255 255 311 267 267 1652 018 263 263 254 254 264 264 255 255 2072 019 266...

Page 39: ...XING Tab 10d Single support code mm Code A B P F CF G L S 270327 82 35 M10 11 0 110 60 128 2 Tab 10e Rubber supports Unit Configuration Support kit code Single support code Kit support pieces CB0 FB0...

Page 40: ...n PART A The capacity of the lifting equipment must be sufficient for the load to be lifted Check the unit weight the load capacity of the balance the chords and the quality of the above mentioned app...

Page 41: ...04 022 4000 1438 578 1444 CG0 006 2000 837 598 723 007 3000 1211 598 888 009 3000 1231 597 934 011 3000 1150 567 1049 014 4000 1461 579 1357 015 4000 1446 579 1375 018 4000 1439 578 1418 FB0 006 2000...

Page 42: ...82 1727 019 4000 1808 582 1739 022 4000 1798 581 1779 CG0 006 2000 928 595 843 007 3000 1462 593 1133 009 3000 1468 593 1179 011 3000 1381 569 1294 014 4000 1835 583 1692 015 4000 1819 582 1710 018 40...

Page 43: ...op view Ordinary maintenance area Extraordinary maintenance area UNIT 1000 1000 1000 1000 AIR AIR Notes Minimum distance between 2 units from condensing coil side 2 m Do not obstruct the air exiting t...

Page 44: ...0 90 1332 2006 37 A 1642 239 5 466 936 5 Chilled water inlet R 2 ISO 7 1 Chilled water outlet R 2 ISO 7 1 45 122 Electrical panel and control unit Rear front removable panel Prepunched for supply cabl...

Page 45: ...Prepunched for supply cables inlet N 2 2 x 63 N 1 1 x 36 Lateral view Supply cable inlet See front view Front view Electrical panel and control unit Rear front removable panel Prepunched for supply c...

Page 46: ...1 1 x 36 Front view Lateral view Electrical panel and control unit Rear front removable panel Prepunched for supply cables inlet N 2 x 63 N 1 x 36 Supply cables inlet Removable panel fixed by screws A...

Page 47: ...ead coupling X Tab 12 Refrigerant circuit components HPC S 006 022 R410A Pos Description Pos Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch Transducer pressure sensor Low...

Page 48: ...L Fig 13a CHILLER HYDRAULIC DIAGRAM A Tread coupling Tab 13a Chiller hydraulic components HPC S 006 022 R410A Pos Description Pos Description 1 2 3 4 5 6 7 8 9 Evaporator Evaporator water outlet senso...

Page 49: ...7 12 10 5 4 18 A Tread coupling Tab 13b Freecooling hydraulic components HPC S 006 022 R410A Pos Description Pos Description 1 2 3 4 5 6 7 8 9 Evaporator Evaporator water outlet sensor antifreeze Evap...

Page 50: ......

Page 51: ...me a las directivas Europeas O Fabricante declara que este produto est em conformidade com as directivas Europeias Tillverkare f rs krar h rmed att denna produkt verensst mmer med Europeiska Uniones d...

Page 52: ...asing IT system availability flexibility and efficiency For more information visit www liebert com www emersonnetworkpower com or www eu emersonnetworkpower com While every precaution has been taken t...

Reviews: