2
Model Number Description
2 -- 1
Liebert HPC---S 006---022---PD---273571---01.03.2012
Model Number Description
Model Nomenclature / Digit Numbers
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18
Cooling Capacity
Cooling capacity (x 10 = kW)
Refrigerant
0
= R410A
Versions
B
= Base version
G
= High efficiency class version
Specification
C
= Air cooled
Chiller
F
= Freecooling
Chiller
G 0 0 1
C
1
Liebert HPC---S 006---022
Digits 1, 2, 3, 4, 5, 6 --- Base unit
Base unit main features
D
R410A refrigerant;
D
One refrigeration circuit;
D
HP and LP gauges;
D
Fans speed control (TRIAC or EC according
B
or
G
version); on
B
versions, different options with EC fans
are available;
D
On digit 11 base version
B
, opt. B & D +
G
version
opt. C compressors jacket if necessary;
D
On digit 11
G
version opt. D compressors
compressor’s box insulated if necessary;
D
Expansion valve:
TXV
(Thermostatic expansion
Valve) on
B
version;
EEV
(Electronic Expansion Valve)
on
G
version;
D
Flow switch and Hydraulic Kit (Hydraulic Kit =
expansion vessel and safety valve);
D
Evaporator electric tank electric heater will
protect piping too (only if pump/s are fitted on unit);
D
Electrical panel ventilation;
D
Buffer tank of 100, 200 and 300 litres (1, 2 and 3 fans).
Digit 7 --- Display and Switch
A
= FTE display
B
=FTE d Network Switch
E
= iCOM Coldfire display large
F
= iCOM Coldfire display large + Network Switch
Digit 8 --- Soft starter
0
= None
1
= With compressors soft starter
Digit 9 --- Monitoring
0
= None
1
= IS Housing (no IS Card included)
2
= Web card
3
= Modbus card
4
= Sitescan card
5
= Web card + Modbus card
6
= Web card + Sitescan card
7
= Modbus card + Sitescan card
8
= Bacnet card (Bacnet or Modbus over IP)
Digit 10 --- Buffer tank
0
= None
1
= With buffer tank
2
= With buffer tank + electric heaters (only for chiller
models)
Digit 11 --- Fans options
A
= TRIAC control and 900 mm fans
B
=TRIAC control and 800 mm fans
C
=EC---Fans, 900 mm
D
=EC---Fans, 800 mm
Digit 12 --- Pumps group
(expansion tank and water
safety valve always included as standard)
1
= No pumps
2
= With 1 pump LP (low pressure)
3
= With 1 pump HP (high pressure)
4
= With 2 pumps LP (low pressure)
5
= With 2 pumps HP (high pressure)
Digit 13 --- Free
Digit 14 --- Electric panel options
0
= None
1
= With electric heaters
A
= Fast start ramp
B
=Fast start ramp and electric heaters
Digit 15 --- Evaporator antifreeze protection
0
= None
1
= With evaporator antifreeze protection
2
= With evaporator and pipe antifreeze protection
Digit 16 --- Compressor power factor correction
0
= None
1
= With compressors power factor capacitors
Digit 17 --- Coil metal filter / Protection grid
0
= None
1
= With coil metal filter
Digit 18 --- Special requests
0
= None
X
= As specified
Summary of Contents for HPC-S 006