20 Chapter 3 Electrical Installation
Liebert NXC 30kVA And 40kVA UPS User Manual
Figure 3-4 Power cables wiring route (bottom cable access)
Connection steps
Warning
Before cables connection, make sure that all external and internal power switches of the UPS are off, and post necessary warning
signs to prevent inadvertent operation of the switches. Meanwhile, measure the voltages between the UPS terminals and the
voltages between the terminals and the earth.
Refer to Figure 3-2 ~ Figure 3-4, connect the power cables as described in the following procedures:
1. Open the front door of the UPS, and remove the protective cover (located at the lower left corner) to reveal the
power cable connection terminals (see Figure 3-2).
2. Connect the protective earth cable to the PE input terminal in the cabinet.
Warning
1. The earth cables and neutral line must be connected in accordance with local and national codes of practice.
2. Failure to observe this could result in electric shock or fire risk.
3. Identify and make power connections for the input cables according to one of the following two procedures,
depending on the type of installation.
Connection of common input
1) Connect the AC input cables to the bypass input terminals (bA-bB-bC) in the cabinet, and ensure that the three
shorting copper bars between the rectifier input terminals (mA-mB-mC) and the bypass terminal terminals are
Remove this cover board, lead
cables into the cabinet, and connect
them to corresponding terminals