2.6.2 Low-Voltage Control Wire Sizing
Low-voltage wiring should be sized to allow a 1 volt maximum drop due to line resistance between the
evaporator and condensing unit. Use NEC Class 1 or 2 wiring according to wire routing conditions
chosen, local codes and application limits in
Tables 14
and
15
.
2.7
Electrical Data
Table 15
Recommended minimum wire size
Max. Distance*
ft. (m)
Min. Wire Gauge
AWG (mm
2
)
50 (15)
20 (0.75)
100 (30)
18 (1.0)
150 (45)
16 (1.5)
* One-way control wire run between outdoor condensing unit and evaporator.
Table 16
Electrical data—Standard sound and ambient models (95°F/35°C) 60Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage- Phase
208/230-1
208/230-3
460-3
575-3
14
1
FLA
9.1
—
—
—
WSA
11.0
—
—
—
OPD
15
—
—
—
20
1.5
FLA
12.1
—
—
—
WSA
14.8
—
—
—
OPD
25
—
—
—
27
2
FLA
13.4
—
—
—
WSA
16.4
—
—
—
OPD
25
—
—
—
37
3
FLA
18.5
13.4
7.1
5.8
WSA
22.8
16.4
8.7
7.0
OPD
35
25
15
15
42
3.5
FLA
—
15.0
7.1
6.0
WSA
—
18.4
8.7
7.2
OPD
—
30
15
15
67
5
FLA
—
24.1
11.7
9.1
WSA
—
29.3
14.2
11.1
OPD
—
45
20
15
96
8
FLA
—
36.2
18.1
13.4
WSA
—
41.4
20.6
15.3
OPD
—
60
30
20
*
FLA
= Full Load Amps
WSA
= Wire Size Amps (minimum supply circuit current capacity)
OPD
= Overcurrent Protection Device (fuse or circuit breaker)