8

If  the  UPS  fails  to  operate  properly,  turn  off  the  unit  and  repeat  the  steps  in  the
installation section of this manual.  If the problem persists, refer to the chart below:

PROBLEM

POSSIBLE CAUSE

REMEDY

No indication, no

Check building wall outlet and mains cable by

beep even UPS is

No input voltage

connecting another device with cable to this wall 

connected to mains

outlet

power supply

Fuse has been melt

Replace fuse by fuse with same rating

Green LED blinks,

Mains power failure

Wait until mains power recovers

red LED off,

UPS input power cord

Make sure the power cord is connected

1 beep every 4 sec.

not plugged in
Power cord defective

Please contact your dealer

Plug the UPS into a working wall outlet for at least

Grenn LED blinks,

very low battery voltage

8 hours to recharge the batteries. If the problem

red LED off,

still rmains, the UPS will not operate during

1 beep every sec.

power failure, or it will turn off immediately. In this
case, contact your dealer

Grenn LED lights up,
red LED blinks,

Battery cannot be charged

Please contact your dealer

2 beep every 2 sec.

Grenn LED lights up,
red LED blinks,

The power required from

Remove equipment until the UPS stops beeping

1 beep every half-

the equipments is too high

sec.

Green LED off,

Output short circuit

Remove alla off the equipments and contact your dealer

red LED lights up,

Overload exceeds 120%

Reduce the load

continuous beeps

UPS fault

Contact your dealer

TROUBLESHOOTING

Summary of Contents for PowerSure Personal XT 1250 VA

Page 1: ...450 700 1250 VA 230V PowerSureTM Personal XT USER MANUAL English Deutsch Fran ais Italiano Espa ol...

Page 2: ...OR OTHER APPLICATIONS Store in safe place if not required at this time 4 This UPS must be earthed at all times during operation Connect only to a mains supply socket outlet with an earth connection A...

Page 3: ...stable cart stand or table Do not place UPS under direct sunlight or close to heat emitting sources Do not place UPS power cord in any area where it may get damaged by heavy objects Follow all warning...

Page 4: ...ovides conditioned power to microcomputers and other sensitive electronic equipment PowerSure OUTPUT Lead acid battery inside the enclosure Blei Akkumulator innerhalb des Gehause INPUT FUSE 250V 5A T...

Page 5: ...0V 50 60Hz 4 0A 1 OUTPUT 230V 50 60Hz 700VA 420W 3 1A MADE IN CHINA Remove from Box Remove Plug from Units and replace in UPS Press ON Button Plug Units s into UPS 110 mm 0 40 C Check for Damage OUTPU...

Page 6: ...EDs of the front panel will light up for 2 seconds The green light up continuously This indicates normal operation Note If the UPS continues to beeps or the green light is not alight even mains power...

Page 7: ...c 1 beep every 4 sec Power failure UPS is battery mode 1 beep every sec Battery low UPS is in battery mode batteries are nearly axhausted and UPS will be shut down 1 beep every 2 sec Battery weak UPS...

Page 8: ...n Power cord defective Please contact your dealer Plug the UPS into a working wall outlet for at least Grenn LED blinks very low battery voltage 8 hours to recharge the batteries If the problem red LE...

Page 9: ...itter 8 AC Fail open emitter 9 AC Fail open collector The DB 9 communication port allows the status of UPS to be monitored data to be backed up computer to be switched off COMMUNICATIONS The PowerSure...

Page 10: ...20 load 20s to shutdown Battery mode 120 load 5s to shutdown BATTERY PARAMETERS Model Number PSPXT450 230 PSPXT700 230 PSPXT1250 230 Type Valve regulated nonspillable lead acid Quantity x Voltage x 1...

Page 11: ...ident abuse neglect negligence unauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a ma...

Page 12: ...han 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service...

Reviews: