2

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that should be followed during the
installation and maintenance of the UPS and its batteries.  Please read this manual
thoroughly before attempting to install or operate this UPS.

This equipment can be installed and operated by individuals without previous training.

1.  PowerSure Personal models are available for 115VAC and 230VAC supply voltages and

loads.  Please verify that this model matches your AC mains/ load voltage requirements.

2.  This equipment is designed for Commercial/Industrial use only. Liebert Corporation

neither recommends nor knowingly sells this product for use in critical life support
applications.

 

3.  The PowerSure Personal 230VAC models are not supplied with an input power lead for

connection to the mains supply. Use the input mains power lead from your data
processing equipment to connect the UPS to the mains supply. The UPS is supplied with
two output power leads with moulded connectors to connect from the UPS output to your
equipment. Additional input/output leads can be obtained from your dealer.
Also provided is a Liebert special interconnection cable for connection to DB9 connector
on the rear of the UPS for use with Liebert’s SiteNet MultiLink® software (see user
manual for details) DO NOT USE FOR OTHER APPLICATIONS.  Store in safe place if
not required at this time.

4.  This UPS must be earthed at all times during operation. Connect only to a mains supply

socket outlet with an earth connection. A means of disconnection of the mains supply
should be within 2 metres of the UPS.

5.

WARNING: Output receptacles on the UPS are electrically live if the UPS is switched
ON, even if the UPS is not plugged in to a mains supply. The On/Off button on the UPS
does not electrically isolate the internal parts. To isolate the UPS, switch OFF the UPS
first, then unplug it from the mains.

ƒ

 

To reduce the risk of electric shock, do not remove the cover, as it has no user-
serviceable parts inside.  Some components are live, even when AC power is
disconnected.  For service, contact a qualified technician.

ƒ

 

To reduce the risk of fire, use the proper rating when replacing the fuse.

ƒ

 

To prevent the risk of fire or electric shock, install the UPS in a temperature and humidity
controlled room, free of conductive contaminants.

6.  Your total load earth leakage current must not exceed 2.75 milli-amperes. Most data

processing equipment meets this requirement if you use no more than 2 pieces of
equipment. For further advice contact your dealer.

7.  The UPS relies on your building wiring overcurrent protection, which must be rated

between 10-20 amperes.

8.  When using the communication features on the UPS, ensure the cabling connected to

the DB9 communication port or the network connection are kept separated by 25mm
from the power leads to the UPS input and output.

Summary of Contents for PowerSure Personal

Page 1: ...USER MANUAL 300 500 VA 230V POWERSURE PERSONAL...

Page 2: ...FOR OTHER APPLICATIONS Store in safe place if not required at this time 4 This UPS must be earthed at all times during operation Connect only to a mains supply socket outlet with an earth connection...

Page 3: ...cart stand or table Do not place UPS under direct sunlight or close to heat emitting sources Do not place UPS power cord in any area where it may get damaged by heavy objects Follow all warnings and i...

Page 4: ...ptible Power System UPS It provides conditioned power to microcomputers and other sensitive electronic equipment MAJOR COMPONENTS Mains Battery LED Warning LED Liebert R P er sonal Pow erSure TM Power...

Page 5: ...Per sonal Pow erSure TM Check for Damage Liebert R Per sonal Pow erSure TM Liebert R Per sonal Pow erSure TM 110 mm 0 40 C Press ON Button for 2 seconds Remove Plug from Unit and replace in UPS Plug U...

Page 6: ...ated green 6 Check the operation of your load equipment it should display normal operational conditions 7 If any function provides an abnormal condition refer to the trouble shooting guide later in th...

Page 7: ...inuous Beep UPS Failure Battery Mode Mode Green Red Alarm Indicates Back Up Flash Every 3 sec OFF Beep Every 3 sec UPS is on Battery UPS Fault Flash Every 3 sec ON Continuous Beep No Output Low Batter...

Page 8: ...voltage below threshold AC overvoltage Plug in power cord securely Replace fuse and restart UPS Call a qualified electrician Wait until voltage rises to appropriate level Voltage must be higher than...

Page 9: ...eral signals are provided on this port and are assigned as follows PIN ASSIGNMENT DESCRIPTION 1 Low Battery open collector 2 No connection 3 No connection 4 On Battery Mode Shutdown 5 12V DC 5 On Batt...

Page 10: ...t and pull fuse holder out to remove AC Inlet Fuse Holder Input Fuse Spare Fuse CAUTION Before changing the supply fuse turn off the UPS and unplug the input mains lead from the AC mains socket and fr...

Page 11: ...Utility and Battery Modes Overload Warning 15 25 W Overload Warning 20 45 W BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 1 x 12V x 4 5 Ah 1 x 12V x 7 0 Ah...

Page 12: ...ident abuse neglect negligence unauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a ma...

Page 13: ...e than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Servi...

Reviews: