250 VA LED & ALARM INDICATIONS 

Condition 

Green AC 

Light (4) 

Audible Alarm 

Status 

NORMAL/START UP 

On after Beep 

Single Beep, then Off 

Operate 

Start-Up Test Fail 

On after Beep 

Fast Beep for 15 Sec and then Off 

Operate* 

Input Frequency Mismatch with 
Option Switch Setting 

 

Input Voltage Below Threshold 

 

Off 

 

Continuous 

 

Will Not Start 

Overload/Short Circuit 

Off 

Continuous for 15 Sec and then Off 

Will Not Start 

NORMAL MODE 

On 

Off 

Operate 

Battery Test Fail 

On 

Fast Beep for 15 Sec and then Off 

Operate 

Overload/Short Circuit 

Off 

Continuous for 15 Sec and then Off 

Shutdown 

BACKUP MODE 

Off 

Slow Beep 

Operate 

Low Battery Alarm 

Off 

Fast Beep 

Warn of Shutdown 

Low Battery Shutdown 
Overload/Short Circuit 

 

Off

 

 

Continuous for 15 Sec and then Off 

 

Shutdown

 

Utility Overvoltage 
(transfer enabled) 

 

Off 

 

 

Slow Beep 

 

 

Operate 

 

  *The UPS starts and repeats the battery test sequence every hour until the test is passed. 

 

 

400/600 VA LED & ALARM INDICATIONS 

 

Condition 

Green AC  

Light (4)

 

Amber 

Battery  

Light (2)

 

Red 

Warning  

Light (3)

 

 

Audible Alarm 

 

Status 

NORMAL/START UP 

On 

Flash Once & 

then Off 

Off 

Single Beep and then 

Off 

Operate 

Start-Up Test Fail 

Off 

Off 

On 

Continuous for 15 

Sec and then Off 

Will Not Start 

Input Frequency Mismatch 
with Option Switch Setting 
 
Overload/Short Circuit 

 

Off 

 

On for 15 

Sec and 

then Off 

 

Flash 

 

Continuous for 15 

Sec and then Off 

 

Will Not Start 

Input Voltage Below 
Threshold 

Off 

Off 

Flash 

Continuous for 15 

Sec and then Off 

Will Not Start 

NORMAL MODE 

On 

Off 

Off 

Off 

Operate 

Battery Test Fail 

On 

Off 

On 

N/A 

Operate 

Overpower 

On 

Off 

Flash 

Fast Beep 

Alarm Only 

Overload/Short Circuit 

Off 

On for 15 

Sec & then 

Off 

Flash for 15 

Sec & then 

Off 

Continuous for 15 

Sec & then Off 

Shutdown 

Charger Fail 

On 

Off 

On 

Slow Beep 

Alarm Only 

BACKUP MODE 

Off 

On 

Off 

Slow Beep 

Operate 

Low Battery Alarm 

Off 

On 

On 

Fast Beep 

Operate 

Low Battery Shutdown 

Off 

On* 

On* 

Continuous for 15 

Sec & then Off 

Shutdown 

Utility Undervoltage 

Off 

On 

Off 

Slow Beep 

Operate 

Utility Overvoltage 

Off 

On 

Flash 

Slow Beep 

Operate 

Overload/Short Circuit 
SiteNet 1 Shutdown 

Off 

On* 

Flash* 

Continuous for 15 

Sec & then Off 

Shutdown 

*If there is insufficient utility voltage, this indicator illuminates for 15 seconds then turns off to preserve the battery.

 

Summary of Contents for PowerSure PS250-60S

Page 1: ...PowerSure POWER PROTECTION Uninterruptible Power System 250 VA 600 VA 115 V USER S MANUAL English R PS250 60S 250 VA PS400 60S 400 VA PS600 60S 600 VA...

Page 2: ...es or corrosive substances 6 WARNING Do not modify cable Consult dealer if connector does not match equipment UPS must be grounded at all times while in use Turn UPS OFF before unplugging or the safet...

Page 3: ...art up The UPS resets the counter after back up operation manual battery test or if the UPS is switched OFF The operator may perform a manual battery test by pressing the BATTERY TEST button on the ba...

Page 4: ...If any appear faulty or damaged contact your dealer immediately Store the packaging in a safe place for possible future shipment of UPS 3 Place the UPS on a sturdy dry surface in a well ventilated ar...

Page 5: ...be unlit 5 Check the operation of your equipment It should display normal operational conditions 6 If any function provides an abnormal condition refer to the troubleshooting guide later in this manu...

Page 6: ...NDOWS and many others SiteNet 1 software automatically performs an orderly shutdown of computer operating systems in the event of a power outage and or low battery conditions The SiteNet 1 kit supplie...

Page 7: ...s at 140VAC Factory setting is 135 VAC Option Switch 3 4 Low Voltage Transfer Select Low voltage transfer is the voltage level at which battery operation starts You may set the low voltage transfer of...

Page 8: ...OFF UPS and unplug it from utility supply CAUTION Observe proper precautions When replacing batteries use the same number and type of batteries Proper battery disposal required Refer to local codes f...

Page 9: ...ity overvoltage Wait until utility voltage rises to appropriate level Check circuit breaker at rear of UPS 9 If it is activated reset it and restart the UPS See Resetting Circuit Breaker If problem pe...

Page 10: ...Audible Alarm Status NORMAL START UP On Flash Once then Off Off Single Beep and then Off Operate Start Up Test Fail Off Off On Continuous for 15 Sec and then Off Will Not Start Input Frequency Mismat...

Page 11: ...Hz 57 63 Hz Output Voltage on battery 115 VAC 5 Output waveform on battery Stepped Sine Wave Max Output Current at 120 V 2 1 A 3 3A 5 A Output Frequency 50 or 60 Hz 5 Max Overload Capacity 115 of Powe...

Page 12: ...unauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanyi...

Page 13: ...ecaution has been taken to ensure accuracy and completeness in this manual Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information...

Reviews: