background image

PowerSure PSA

Guide Specification

350 – 1000VA

SL-23271 8/03

3

127 VAC nominal: single phase, 2-wire-plus-ground: 90 

 150 VAC (±3VAC),

Buck compensation: 141VAC (±3VAC)
Boost1 compensation: 113VAC (±3VAC)
Boost2 compensation: 100VAC (±3VAC)

220 VAC nominal: single phase, 2-wire-plus-earth: 155 

 270 VAC (±6VAC)

Buck compensation: 243 VAC (±6VAC)
Boost1 compensation: 197 VAC (±6VAC)
Boost2 compensation: 174 VAC (±6VAC)

230 VAC nominal: single phase, 2-wire-plus-earth: 163 

 282 VAC (±6VAC)

Buck compensation: 254 VAC (±6VAC)
Boost1 compensation: 207 VAC (±6VAC)
Boost2 compensation: 183 VAC (±6VAC)

240 VAC nominal: single phase, 2-wire-plus-earth: 171 

 291 VAC (±6VAC)

Buck Compensation: 265 VAC (±6VAC)
Boost1 compensation: 215 VAC (±6VAC)
Boost2 compensation: 191 VAC (±6VAC)

B. 

 

Frequency:

 The UPS automatically senses the input frequency and operates within the

following frequency specifications without drawing power from the batteries.

 
 

50 Hz Applications

:  46.5 

 53.5 Hz (±0.1 Hz)

 

60 Hz Applications

:  56.5 

 63.5 Hz (±0.1 Hz)

 

C. 

 

Surge Protection:

 The 120 VAC units can withstand input surges of up to 570J without

damage per criteria listed in IEEE C62.41, Category A, Level 3.  The 230 VAC units can
withstand input surges of up to 660J without damage per criteria listed in EN61000-4-5,
Level 3, Criteria A.

D. 

 

Input Connections: 

The 120 VAC units have an attached input cord 6.0 feet (1.8 meters) in

length, measured between the inside edges of the connectors.  The attached input cord has a
NEMA 5-15 plug. 

1.3.3.2

 

AC Output

A.

 

Voltage Configuration: 

120 VAC units:  110/120/127 VAC, 60/50 Hz, single-phase, 2-wire-plus-ground.

120VAC ± 8% (Battery mode)

230 VAC units:  220/230/240 VAC, 50/60 Hz, single phase, 2-wire-plus-earth.

230 VAC ±8% (Battery mode)

B. Voltage Regulation: 

±10% steady state.

C. Frequency Regulation:

 +0.1Hz synchronized to utility / mains.

+0.5Hz free running or on battery operation.

D.

 

Load Power Factor Range:

 0.6 lagging to 1.0 (unity).

E. Inverter Overload Capability:

 Overload Warning (visual and audible alarms) occurs

between 100%

109% of rated capacity, continuous duty. Shutdown occurs at the following

levels:           >110 

 120%; after 120 seconds (Normal mode)

>120 

 150%; after 15 seconds (Normal mode)

>150% - short-circuit; after 5 seconds (Normal mode)

>110%; after 2 cycles (Battery mode)

Summary of Contents for PowerSure PSA 350VA to 1000VA

Page 1: ...herein the statements in this specification will govern 120V Units UL 1778 c UL listed to CSA 22 2 No 107 1 FCC Part 15 Subpart B Class B ANSI C62 41 Category A Level 3 IEEE 587 Category A EN61000 4 5 Level 3 Criteria A EN61000 4 2 Level 3 Criteria A EN61000 4 3 Level 3 Criteria A EN61000 4 4 Level 4 Criteria A EN61000 4 6 Level 3 Criteria A EN61000 3 2 EN61000 3 3 ISTA Procedure 1A 230V Units EN5...

Page 2: ... specifications of the UPS are Input 120V Units 0 160 VAC 60 50 Hz auto sensing single phase 2 wire plus ground 230V Units 0 300 VAC 50 60 Hz auto sensing single phase 2 wire plus earth Output 120V Units 110 120 127 VAC 10 60 50 Hz single phase 2 wire plus ground DIP Switch selectable 230V Units 220 230 240 VAC 10 50 60 Hz single phase 2 wire plus earth DIP Switch selectable B Output Load Capacity...

Page 3: ...its can withstand input surges of up to 570J without damage per criteria listed in IEEE C62 41 Category A Level 3 The 230 VAC units can withstand input surges of up to 660J without damage per criteria listed in EN61000 4 5 Level 3 Criteria A D Input Connections The 120 VAC units have an attached input cord 6 0 feet 1 8 meters in length measured between the inside edges of the connectors The attach...

Page 4: ...xceed 40dB when measured at 1 meter from the surface of the UPS A weighted E Electrostatic Discharge The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and without affecting the connected load The 230 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and wi...

Page 5: ...e UPS cabinet is injection molded standard color Dimensions and weights are UNIT UNIT DIMENSIONS W x D x H in mm 120 VAC UNITS WEIGHT lbs kg 230 VAC UNITS WEIGHT kg lbs 350VA 4 6 x 7 7 x 8 7 116 x 196 x 222 16 8 7 6 7 15 4 500VA 4 6 x 7 7 x 8 7 116 x 196 x 222 17 2 7 8 7 4 16 3 650VA 4 6 x 14 1 x 8 7 116 x 358 x 222 20 7 9 4 9 1 20 1 1000VA 4 6 x 14 1 x 8 7 116 x 358 x 222 29 7 13 5 13 2 19 1 2 1 ...

Page 6: ... 2 2 3 Bi Directional Converter DC Protection The following DC shutdown levels protect the UPS DC Overvoltage Shutdown DC Undervoltage Shutdown End of Discharge DC Undervoltage Warning Low Battery Reserve 2 2 2 4 Output Protection For output faults including short circuits and overloads the UPS is protected by the input circuit protector during Normal mode and by electronic current limiting during...

Page 7: ... than 0 5 sec will start up the UPS and to turn the UPS off the button will need to be depressed for more than 2 sec 2 2 3 4 On Line Battery Test The UPS is provided with an automatic biweekly battery test feature The test ensures the capability of the battery to supply power to the inverter while loaded If the battery fails the test the UPS will display a warning to indicate the batteries need re...

Page 8: ...on settings This shutdown signal 5 12VDC must have a duration of at least 1 5 seconds for the UPS to be shut down The UPS communicates via serial communications using Liebert ESP II protocol The PowerSure PSA has a USB interface port for communication that will work with the built in Microsoft Power Manager software on the user s PC if the PC is so equipped It will provide UPS status and manages t...