PowerSure PSA

Guide Specification

350 – 1000VA

SL-23271 8/03

6

2.2.2

Bi-Directional Converter

2.2.2.1 General

The Bi-Directional Converter incorporates solid-state devices and control circuitry to
convert AC power to regulated DC power for battery charging; and convert DC power
from the battery to regulated and conditioned stepped-sinewave AC power for supporting
the critical load.  The Bi-Directional Converter is a pulse width modulated (PWM)
design.  The Bi-Directional Converter operates in the following modes:

1.

In Normal mode of operation, the Bi-Directional Converter maintains the
battery system at a float charge.

2.

In Battery mode of operation, the Bi-Directional Converter converts DC power
from the battery to regulated and conditioned stepped-sinewave AC power for
supporting the critical load.

3.

In the recharge mode of operation, the Bi-Directional Converter converts AC
power to regulated DC power to recharge the battery.

2.2.2.2 Battery Recharge

The UPS contains a battery recharge rate designed to prolong battery life.  The battery is
constant voltage charged to recharge and maintain the battery in a fully charged state.
Recharge time is 6 hours maximum to 90% rated capacity after discharge into full
resistive load.

2.2.2.3 Bi-Directional Converter DC Protection

The following DC shutdown levels protect the UPS:

DC Overvoltage Shutdown
DC Undervoltage Shutdown (End of Discharge)
DC Undervoltage Warning (Low Battery Reserve)

2.2.2.4 Output Protection

For output faults including short circuits and overloads, the UPS is protected by the input
circuit protector during Normal mode and by electronic current limiting during Battery
mode

.

2.2.2.5 Overload

The UPS is capable of supplying power for overloads exceeding 100% and up to 110%
of full load rating, continuously.  A visual indicator and audible alarm indicate overload
operation.  For greater current demands, the UPS employs circuit protector and electronic
current-limiting protection to prevent damage to components. The UPS is self-protecting
against any magnitude of connected output overload.  The UPS control logic senses and
disconnects the UPS from the critical AC load and clears the protective circuit breaker
during Normal mode.

2.2.2.6 Output Frequency

An oscillator controls the output frequency of the UPS.  The oscillator maintains the
output frequency to + 0.5 Hz of nominal when not synchronized to the utility/mains
source.

2.2.2.7 Battery Over-Discharge Protection

To prevent battery damage due to excessive discharge levels, the UPS control logic
automatically monitors the battery voltage and load level and switches off the output at
the predetermined battery shutdown voltage set point.

Summary of Contents for PowerSure PSA 350VA to 1000VA

Page 1: ...herein the statements in this specification will govern 120V Units UL 1778 c UL listed to CSA 22 2 No 107 1 FCC Part 15 Subpart B Class B ANSI C62 41 Category A Level 3 IEEE 587 Category A EN61000 4 5 Level 3 Criteria A EN61000 4 2 Level 3 Criteria A EN61000 4 3 Level 3 Criteria A EN61000 4 4 Level 4 Criteria A EN61000 4 6 Level 3 Criteria A EN61000 3 2 EN61000 3 3 ISTA Procedure 1A 230V Units EN5...

Page 2: ... specifications of the UPS are Input 120V Units 0 160 VAC 60 50 Hz auto sensing single phase 2 wire plus ground 230V Units 0 300 VAC 50 60 Hz auto sensing single phase 2 wire plus earth Output 120V Units 110 120 127 VAC 10 60 50 Hz single phase 2 wire plus ground DIP Switch selectable 230V Units 220 230 240 VAC 10 50 60 Hz single phase 2 wire plus earth DIP Switch selectable B Output Load Capacity...

Page 3: ...its can withstand input surges of up to 570J without damage per criteria listed in IEEE C62 41 Category A Level 3 The 230 VAC units can withstand input surges of up to 660J without damage per criteria listed in EN61000 4 5 Level 3 Criteria A D Input Connections The 120 VAC units have an attached input cord 6 0 feet 1 8 meters in length measured between the inside edges of the connectors The attach...

Page 4: ...xceed 40dB when measured at 1 meter from the surface of the UPS A weighted E Electrostatic Discharge The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and without affecting the connected load The 230 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and wi...

Page 5: ...e UPS cabinet is injection molded standard color Dimensions and weights are UNIT UNIT DIMENSIONS W x D x H in mm 120 VAC UNITS WEIGHT lbs kg 230 VAC UNITS WEIGHT kg lbs 350VA 4 6 x 7 7 x 8 7 116 x 196 x 222 16 8 7 6 7 15 4 500VA 4 6 x 7 7 x 8 7 116 x 196 x 222 17 2 7 8 7 4 16 3 650VA 4 6 x 14 1 x 8 7 116 x 358 x 222 20 7 9 4 9 1 20 1 1000VA 4 6 x 14 1 x 8 7 116 x 358 x 222 29 7 13 5 13 2 19 1 2 1 ...

Page 6: ... 2 2 3 Bi Directional Converter DC Protection The following DC shutdown levels protect the UPS DC Overvoltage Shutdown DC Undervoltage Shutdown End of Discharge DC Undervoltage Warning Low Battery Reserve 2 2 2 4 Output Protection For output faults including short circuits and overloads the UPS is protected by the input circuit protector during Normal mode and by electronic current limiting during...

Page 7: ... than 0 5 sec will start up the UPS and to turn the UPS off the button will need to be depressed for more than 2 sec 2 2 3 4 On Line Battery Test The UPS is provided with an automatic biweekly battery test feature The test ensures the capability of the battery to supply power to the inverter while loaded If the battery fails the test the UPS will display a warning to indicate the batteries need re...

Page 8: ...on settings This shutdown signal 5 12VDC must have a duration of at least 1 5 seconds for the UPS to be shut down The UPS communicates via serial communications using Liebert ESP II protocol The PowerSure PSA has a USB interface port for communication that will work with the built in Microsoft Power Manager software on the user s PC if the PC is so equipped It will provide UPS status and manages t...

Reviews: