PowerSure PSA
Guide Specification
350 – 1000VA
SL-23271 8/03
7
2.2.3
Display and Controls
2.2.3.1 General
The UPS is provided with a microprocessor-based unit status and control display
designed for convenient and reliable user operation. The status and alarm indicators are
displayed on a status indicator display.
2.2.3.2 System Indicators
There are three (3) status indicators on the front of the UPS (Utility, Battery and Fault)
and one (1) on the rear (Site Wiring Fault):
The Utility Indicator illuminates when the UPS is operating and supplying
power to connected loads: green indicates Normal mode, amber denotes
Buck/Boost mode.
The Battery Indicator illuminates to indicate the UPS is operating on battery
(green) or to signify a battery warning (amber).
The Fault Indicator illuminates when the UPS detects a problem: red for an
internal UPS fault, green for overload and over-temperature conditions.
The Site Wiring Fault Indicator on the rear panel illuminates red when the UPS
detects a line-neutral reversal or a poor neutral-ground bond.
2.2.3.3 On/Off Controls
UPS start-up and shutdown operations are accomplished by the "On/Off/Alarm Silence"
push button located on the front panel of the UPS. Depressing the button for more than
0.5 sec will start-up the UPS and to turn the UPS off the button will need to be depressed
for more than 2 sec
2.2.3.4 On-Line Battery Test
The UPS is provided with an automatic biweekly battery test feature. The test ensures
the capability of the battery to supply power to the inverter while loaded. If the battery
fails the test, the UPS will display a warning to indicate the batteries need replaced. The
battery test feature is user accessible via Multilink.
2.2.4
Internal Battery
Valve regulated, non-spillable, lead-acid cells are used as a stored-energy source for the specified
UPS system. The battery is housed internal to the UPS cabinet, and sized to support the inverter at
rated load and power factor, with ambient temperature of 77
o
F (25
o
C) for a minimum of 5
minutes reserve time. The expected life of the battery is 3 - 5 years or 250 complete discharge
cycles.
2.2.5
Output Distribution
Output distribution is integral to the UPS and is located on the rear of the unit.
UNIT
120 VAC UNITS
230 VAC UNITS
350VA,500
VA,650VA
(4) NEMA 5-15R (orange) Battery
surge protection;
(2) NEMA 5-15R (black) surge
protection only
(4) IEC-320-C13 (orange) Battery backup
+ surge protection;
(2) IEC-320-C13 (black) Surge protection
only
1000VA
(6) NEMA 5-15R (orange) Battery
surge protection;
(2) NEMA 5-15R (black) surge
protection only
(6) IEC-320-C13 (orange) Battery backup
+ surge protection;
(2) IEC-320-C13 (black) Surge protection
only