background image

Business-Critical Continuity

, Emerson Network

Power and the Emerson Network Power logo

are trademarks and service marks of Emerson

Electric Co. ©2008 Emerson Electric Co.

Emerson Network Power.com

Emerson Network Power.

The global leader in enabling

Business-Critical Continuity

.

AC Power

Connectivity

DC Power

Embedded Computing

Embedded Power

Monitoring

Outside Plant

Power Switching & Controls

Precision Cooling

Racks & Integrated Cabinets

Services

Surge Protection

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. & 

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana 

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone 

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone 

852 28029250 FAX

liebert.com

24 x 7 Tech Support

800 222 5877 Phone

614 841 6755 (outside U.S.)

While every precaution has been taken to ensure accuracy and 

completeness in this literature, Liebert Corporation assumes no

responsibility, and disclaims all liability for damages resulting

from use of this information or for any errors or omissions.

© 2008 Liebert Corporation. All rights reserved throughout 

the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks

of their respective owners.

® Liebert is a registered trademark of the Liebert Corporation.

SL-23305 (R12/08)        Printed in USA

Liebert

®

PSA

Specifications

M

odel Number 

PSA500MT3-120U

PSA650MT3-120U

PSA1000MT3-120U

PSA1500MT3-120U

Capacity VA/W

500 / 300

650 / 390

1000 / 600

1500 / 900

Net Weight: lbs (kg)

14.1 (6.4)

14.6 (6.6)

23.8 (10.8)

27.8 (12.6)

Shipping Weight: lbs (kg)

15.9 (7.2)

16.3 (7.4)

26.0 (11.8)

30.0 (13.6)

Dimensions: W x D x H, in. 

3.7 x 14 x 6.7

3.7 x 14 x 6.7

5.8 x 14.2 x 9.2

5.8 x 14.2 x 9.2

(mm)

(95 x 356 x 171)

(95 x 356 x 171)

(147 x 360 x 234)

(147 x 360 x 234)

On-Line Input Voltage

84 -140VAC

On-Line Frequency

50/60Hz ±5Hz

Output Voltage (Utility Power Normal)

Typical 97-129VAC

Output Voltage (Battery Operation)

120VAC ±5%

On-Battery Wave Form

Stepped Sinewave

Typical Recharge Time

6-8 hours to 90%

Battery Run Time*

- Full Load

3-5 minutes

3-5 minutes

6 minutes

6 minutes

- Half Load

10 minutes

10 minutes

12-13 minutes

12-13 minutes

Audible and Visual

Audible alarm / LED

Backup Outlets

NEMA 5-15R (3)

NEMA 5-15R (3)

NEMA 5-15R (6)

NEMA 5-15R (6)

Surge Outlets

NEMA 5-15R (1)

NEMA 5-15R (1)

NEMA 5-15R (2)

NEMA 5-15R (2)

Operating Temperature, ˚F (˚C)

32 to 104 (0 to 40)

Storage Temperature, ˚F (˚C)

5 to 104 (-15 to 40)

Operating / Storage Relative Humidity

0%-90%, non-condensing

EMI Classification

FCC Part 15 Class B

Agency

Safety

UL 1778

c-UL Listed

Transportation

ISTA Procedure 1A Certification

*Battery run time may vary depending on load

500/650 VA back view

1000/1500 VA back view

RJ-45 jack (In/Out) —
data line protection

Surge outlets (2)
NEMA 5-15R

USB Interface

Battery backup outlets
(6) NEMA 5-15R

Input breaker

Plug NEMA 5-15P 

Site Wiring Fault
Indicator

Communications/Shutdown Software:

Windows (98 and later) built-in power management functions

provide monitoring of UPS status and manage the automatic

orderly shutdown of the computer if a power outage ever

exceeds the battery capacity of the UPS. Liebert USB shutdown

and monitoring software is provided.

 

Reviews: