Congratulations on the purchase of the Liebert SiteNet® CommSure™. 
 
The CommSure is a communications interface that permits two Liebert UPSs to 
function together as a redundant, high availability power system.  Computers with 
two or more power supplies are required.  Without the CommSure, false 
communications signals would occur, possibly causing unexpected shutdown of 
computer equipment.  However, with a CommSure installed, computers will 
continue to operate as long as power is available from one UPS or both.  If power 
is unavailable from either UPS, the SiteNet CommSure, using standard Liebert 
software, will automatically shut down your computer(s) in an orderly manner. 
 
The CommSure may be rack mounted or used on a desktop. 
 
Requirements: 

 

• 

Computer(s) with dual power supplies 

• 

Two (2) UPSs, each of which can support the entire load 

• 

SiteNet MultiLink or SiteNet 1 Cable (not included) 

 
Included with the SiteNet CommSure are: 

 

• 

Two (2)  AC input cords with NEMA 5-15P plugs for 120V UPS   

• 

Two (2) AC input cords with IEC320-2-2/E plugs for 230V UPS   

• 

Two (2) DB-9 communication cables 

• 

Two (2) brackets for mounting in 19” racks 

• 

Four (4) rubber feet 

• 

This user’s manual and other literature 

 
If any of the above are not included, please call the appropriate number listed on 
the last page of this manual. 
 
Optional equipment for the SiteNet Commsure include: 

 

• 

Two (2) brackets for mounting in 24” racks 

 

Introduction 

Summary of Contents for SiteNet CommSure

Page 1: ......

Page 2: ...nt the risk of fire or electric shock install the CommSure in a temperature and humidity controlled room free of conductive contaminants CAUTION Although your CommSure has been designed and manufactur...

Page 3: ...rt software will automatically shut down your computer s in an orderly manner The CommSure may be rack mounted or used on a desktop Requirements Computer s with dual power supplies Two 2 UPSs each of...

Page 4: ...4 SiteNet CommSure Components R R 2 SiteNet CommSure Front Back DB 9 to UPS 2 AC power to UPS 2 DB 9 to Computer DB 9 to UPS 1 AC power to UPS 1...

Page 5: ...ng the supplied DB 9 cables connect the UPS to the CommSure Note One end of the cable is labeled CommSure and should be connected to the CommSure unit 5 Connect the center DB 9 communications port on...

Page 6: ...ure and should be connected to the CommSure unit 5 Connect the center DB 9 communications port on the CommSure to the computer using a SiteNet 1 or Multilink cable not included 6 Plug in AC power to b...

Page 7: ...ur computer operates as long as power is available from one UPS If power is not available from either UPS CommSure will ensure that the proper shutdown signal is sent to the computer Attention Althoug...

Page 8: ...2 3 m 9 8 ft IEC 320 2 2 E u IEC 320 C13 coupler ENVIRONMENTAL Operating Temperature 0 C to 40 C 32 F to 104 F Storage Temperature 15 C to 50 C 5 F to 122 F Relative Humidity 0 to 95 non condensing AG...

Page 9: ...nform with the above warranty within the two year warranty period Liebert will repair or replace the UPS at Liebert s option Repairs or replacements are warranted for the remainder of the original war...

Page 10: ......

Reviews: