Vertiv | Liebert® GXT5™ | Installer/User Guide
121
Table 7-16 Battery Run Time in Minutes Model: 6-kVA Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
600
600
100.0
226.0
357.5
489.0
621.0
752.5
884.5
1016.0
1148.0
1279.5
1411.5
20
1200
1200
48.0
107.0
172.0
242.0
312.0
382.0
452.0
522.0
592.0
661.5
731.5
30
1800
1800
29.0
70.0
110.0
154.0
201.5
249.5
297.5
345.5
393.0
441.0
489.0
40
2400
2400
19.5
50.5
81.5
112.5
145.0
181.5
218.0
254.5
291.0
327.5
364.0
50
3000
3000
14.5
38.5
63.5
88.0
113.0
138.5
168.0
197.0
226.5
256.0
285.5
60
3600
3600
11.0
30.0
51.0
72.0
92.5
113.5
134.0
158.5
183.5
208.0
232.5
70
4200
4200
9.0
24.0
42.0
60.5
78.0
96.0
113.5
131.5
152.5
173.5
194.5
80
4800
4800
7.5
20.0
35.5
51.5
67.0
82.5
98.5
114.0
129.5
147.5
166.0
90
5400
5400
6.0
17.0
30.5
44.5
58.5
72.5
86.5
100.5
114.0
128.0
143.5
100
6000
6000
5.5
14.5
26.0
39.0
51.5
64.5
77.0
89.5
102.0
114.5
127.0
Table 7-17 Battery Run Time in Minutes Model: 8-kVA.Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
800
800
75.0
166.0
267.5
369.0
471.0
572.5
674.5
776.0
878.0
979.5
1081.0
20
1600
1600
33.5
79.0
124.5
176.0
229.5
283.0
336.5
390.0
443.5
496.5
550.0
30
2400
2400
19.5
50.5
81.5
112.5
145.0
181.5
218.0
254.5
291.0
327.5
364.0
40
3200
3200
13.0
35.0
59.0
82.0
105.5
128.5
155.0
183.0
210.5
238.0
265.5
50
4000
4000
9.5
26.0
45.0
64.0
82.5
101.0
120.0
139.5
161.5
183.5
206.0
60
4800
4800
7.5
20.0
35.5
51.5
67.0
82.5
98.5
114.0
129.5
147.5
166.0
70
5600
5600
6.0
16.0
29.0
42.5
56.0
69.5
83.0
96.5
110.0
123.5
137.5
80
6400
6400
4.5
13.5
24.0
35.5
48.0
59.5
71.5
83.0
95.0
106.5
118.5
90
7200
7200
4.0
11.5
20.5
30.5
41.0
52.0
62.5
73.0
83.5
94.0
104.5
100
8000
8000
3.5
9.5
17.5
26.5
36.0
45.5
55.5
64.5
74.0
83.5
93.0
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...