Table 7-18 Battery Run Time in Minutes Model: 10-kVA.Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
1000
1000
59.0
129.0
211.0
294.0
377.0
460.0
543.0
625.5
708.5
791.5
874.5
20
2000
2000
25.0
62.5
99.0
136.0
179.5
222.5
266.0
309.5
353.0
396.5
439.5
30
3000
3000
14.5
38.5
63.5
88.0
113.0
138.5
168.0
197.0
226.5
256.0
285.5
40
4000
4000
9.5
26.0
45.0
64.0
82.5
101.0
120.0
139.5
161.5
183.5
206.0
50
5000
5000
7.0
19.0
33.5
49.0
64.0
79.0
94.0
109.0
124.0
140.0
158.0
60
6000
6000
5.5
14.5
26.0
39.0
51.5
64.5
77.0
89.5
102.0
114.5
127.0
70
7000
7000
4.0
12.0
21.0
31.5
42.5
54.0
64.5
75.0
86.0
97.0
107.5
80
8000
8000
3.5
9.5
17.5
26.5
36.0
45.5
55.5
64.5
74.0
83.5
93.0
90
9000
9000
2.5
8.0
15.0
22.5
30.5
39.5
48.0
56.5
65.0
73.0
81.5
100
10000
10000
2.0
7.0
13.0
19.5
26.5
34.5
42.0
50.0
57.5
65.0
72.5
Table 7-19 Battery Run Time in Minutes Model: 16-kVA.Models
LOAD
INTERNAL
BATTERY
ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1
2
3
4
5
6
7
8
9
10
%
VA
W
Minutes
10
1600
1600
79.0
176.0
283.0
390.0
496.5
603.5
710.5
817.5
924.0
1031.0
1138.0
20
3200
3200
35.0
82.0
128.5
183.0
238.0
293.0
348.0
403.5
458.5
513.5
568.5
30
4800
4800
20.0
51.5
82.5
114.0
147.5
184.5
221.5
258.5
295.5
332.5
369.5
40
6400
6400
13.5
35.5
59.5
83.0
106.5
130.5
157.5
185.5
213.5
241.5
269.0
50
8000
8000
9.5
26.5
45.5
64.5
83.5
102.5
121.5
141.5
164.0
186.5
209.0
60
9600
9600
7.5
20.5
36.0
52.5
68.0
84.0
100.0
115.5
131.5
150.0
168.5
70
11200
11200
6.0
16.5
29.5
43.5
57.5
71.0
84.5
98.0
112.0
125.5
140.5
80
12800
12800
5.0
14.0
24.5
36.5
49.0
61.0
73.0
85.0
97.0
109.0
121.0
90
14400
14400
4.0
11.5
21.0
31.0
42.0
53.0
63.5
74.5
85.0
95.5
106.5
100
16000
16000
3.5
10.0
18.0
27.0
36.5
46.5
56.5
66.0
75.5
85.0
94.5
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...