Vertiv | Liebert® GXT5™ | Installer/User Guide
33
2.6.2. Terminal-block Connections
On 5-kVA and 10-kVA models, the hard-wire connections to the terminal blocks are made through knockouts
on the POD attached to the rear of the unit. See
Removable Power Distribution Box
, for the
location of the input/output knockouts on your GXT5 model. Models below 3000 VA use input cords with plugs
instead of terminal block connections.
below details the electrical-connection specifications.
Table 2-3 Terminal-block electrical specifications
UPS MODEL
RECOMMENDED
E
XTERNAL
OVER
CURRENT
PROTECTION
RECOMMENDED WIRE
SIZE (INCLUDING
GROUND WIRE) (75°C
COPPER WIRE)
MAXIMUM WIRE SIZE
ACCEPTED BY TERMI-
NAL BLOCK
TERMINAL
TIGHTENING
TORQUE
GXT5-5000IRT5UXLN
40 A
8 AWG
6 AWG
20 in.-lb (2.26
Nm)
GXT5-5000IRT5UXLE
GXT5-6000IRT5UXLN
50 A
GXT5-6000IRT5UXLE
GXT5-8000IRT5UXLN
63 A
6 AWG
GXT5-8000IRT5UXLE
GXT5-10KIRT5UXLN
GXT5-10KIRT5UXLE
GXT5-16KIRT9UXLN
1-phase: 140 A
3-phase: 50 A
35 mm
2
(1 AWG)
53.5 mm
2
(1/0 AWG)
110 in.-lb (12.4
Nm)
GXT5-16KIRT9UXLE
GXT5-20KIRT9UXLN
1-phase: 160 A
3-phase: 63 A
GXT5-20KIRT9UXLE
To make the terminal-block connections:
1. Loosen the screws from the cable-entry/conduit-box cover, and pull the cables through the knockout leaving
some slack for connection.
• We recommend using the knockouts to install input and output wiring in separate conduit. You must
use a suitable cable gland or risk electric shock.
2. Referring to the appropriate terminal-block connection instructions, connect the cables to the corresponding
input/output terminals and use a torque wrench to turn the screw clockwise until tightened as specified in
above.
Summary of Contents for Vertiv GXT5
Page 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Page 8: ...Important Safety Information 2 This page is intentionally left blank ...
Page 30: ...GXT5 Description 24 This page is intentionally left blank ...
Page 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Page 60: ... 52 This page is intentionally left blank ...
Page 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Page 108: ...Maintenance 100 This page is intentionally left blank ...
Page 112: ...Troubleshooting 104 This page is intentionally left blank ...
Page 132: ...Specifications 124 This page is intentionally left blank ...