PHASE 2

PROGRAMMING THE TRAVEL

PHASE 1

PROGRAMMING THE CONTROL UNIT

DEFINING THE STOP PLATES

Ensure that the automation’s opening and closure stop plates have been fixed.

1

2

F

F

O

230V

OFF

1

3

ON

ON

230V

2

O

F

F

230V

N.B. In case just one motor is utilised, choose from Menu Options 2 “Activate single motor” and connect on terminals 20-21-22

b)   Press 

for 5 seconds, the 5 LEDs  will light and 

      then start flashing.
c)   Press

 and the gate starts rolling, if it opens

       press again 

 to invert the movment.

      The first activated limit switch has to be the one of the

      closing system.
Finished the two flash programming 
green LED will be lit and a steady light led the two 
reds. 
If the result was not satisfactory, you can 
perform a programming manual to determine the 
lags.  See Section 3.3.4

a)   Position the leaf gates at 45°.

STOP PLATES    - 

Ensure that the open and close stop plates are set to the correct position

SINGLE MOTOR - 

In the case of a single gate installation connect the motor into terminals 20-21-22

                            before programming enter the options 2 menu and select single motor activated (led 4 

on)

AUTOMATIC  PROGRAMING

POWERING UP 

- With the power off, hold the start button down ,reinstate the power supply and release the 

                           button the red led’s will fl ash

Secs

PHASE 2

PROGRAMMING THE TRAVEL

a)   Press start 

or 5 seconds, the 5 LEDs  will light and 

      then start flashing.
b)   Press

and the gate starts rolling,

 if it open  press again o

 the movment.

      The first activated limit switch has to be the one of the

      closing system.

The automation will perform, in sequence, a closure 

(1)

,

an opening 

(2)

, a closure 

(3)

.

Once programming is complete, the two green LEDs will

flash and the red led 

( )

 will light.

Should the result obtained not be satisfactory, repeat the 

whole process.

S

E

LOS

C

S

N

E

OP

S

E

S

O

L

C

1

2

3

Ensure gate is in central position (half open) and 

  manual release is locked before proceeding

Energy Saving 

In order to save energy, we have introduced the function 

    Energy Saving. 10 minutes after the end of programmation of the control board, the LED 

    of the keyboard go out and it is no more possible to use the control board. To get the control 
    board working again, switch it off and on. 

PROGRAMMING THE TRAVEL

a)   Press start 

or 5 seconds, the 5 LEDs  will light and 

      then start flashing.
b)   Press

and the gate starts rolling,

 if it open  press again o

 the movment.

      The first activated limit switch has to be the one of the

      closing system.

The automation will perform, in sequence, a closure 

(1)

,

an opening 

(2)

, a closure 

(3)

.

Once programming is complete, the two green LEDs will

flash and the red led 

( )

 will light.

Should the result obtained not be satisfactory, repeat the 

whole process.

N.3 Not for RG1R DL UNI version.

Summary of Contents for ACER AC12

Page 1: ...ACER DL E D I S N I L I O AC8R DL AC12R DL ELECTROMECHANICAL OPERATOR FOR SLIDING GATES INSTRUCTIONS FOR INSTALLATION USE AND MAINTENANCE ...

Page 2: ...LLATION AC001 R E C A i n o i z u r t s i i d e l a u n a M R E C A i n o i z u r t s i i d e l a u n a M R E C A Fig 1 Components and devices of a typical automation Fig 2 Description of the contents of the ACER pack ...

Page 3: ... BATTERY NOT PROVIDED BATTERY NOT PROVIDED C from 20 a 70 from 20 a 70 horizontal with dedicated anchorage plate LIFE home integration reserves the right to make changes to technical characteristics at any time and without prior notice without changing its intended use and function TECHNICAL FEATURES for 2 Ah batteries optional and installed Attention The fitter must permanently fix the label desc...

Page 4: ...sions in fig 2 Left Hand Right Hand ATTENTION If the operator is subject to heavy work conditions or if the weight of the leaf is over 300 kg the anchorage plate 1 must be sunk into the concrete b Observe the orientation in fig 3 for positioning the operator anchorage plate R L c Refer to fig 2 2 for the respective heights for 16 or 18 tooth pinions d Lay the electric cable pipes 4 allowing them t...

Page 5: ...ig 5 2 c Definitively fasten the operator by blocking the 4 M10 screws 7 and the relative washers with a fixed or tube wrench 10 Assemble the covers on the clamping feet 4 See fig 5 3 1 4 Installing operator components rack assembly Assemble the gate open A and gate closed B limit switch brackets at the ends of the rack fastening them with the screws provided in the pack as indicated in fig 6 Reme...

Page 6: ...fore the earth wire 2 2 Introducing the electric wires into the operator a To access the ECU remove the cover 2 of the reduction gear removing the two lateral clamping screws 1 b Open the pre punched holes in the cable gland door 3 insert the cable glands 17 then insert the cables 18 needed for the connections keep 230 V and very low voltage cables separate Leave the cables about 40cm longer c Ass...

Page 7: ...g the operator If doubts arise during installation contact a PROFESSIONAL FITTER or the MANUFACTURER Do not perform adjustments and or parameter memorisation before installation is complete and only if you have understood the procedures described in this manual Only mount the operator on gates that are perfectly aligned with the sliding tracks and are properly hung A gate that is not correctly ali...

Page 8: ...e maintenance procedures as described in this manual This is the owner s duty Any checking maintenance or repair work must be conducted by a PROFESSIONAL FITTER Always switch of the electricity supply in the event of malfunctions breakdowns and before any other operations in order to avoid the gate from being activated The owner is not authorised to remove the operator lid as it contains live part...

Page 9: ...9 SPECIFIC DESCRIPTION ACER ...

Page 10: ... AC8R 5RI2420000 AC4R AC4R 5RI2430000 AC6R AC6R 5RI2440001 AC3RMDL 5RI2450000 AC4 24 5RI2460000 AC6 24 5RI2470000 AC8 24 5RI2480000 ACER R 5RI2490000 ACER RM 5RI2500000 ACER 5RI2510000 AC4 AC4R 5RI2520000 AC8 AC4 24 AC6 24 AC8 24 AC3RM24DL AC6RM24DL AC6 AC6R 5RI2530000 ACER 5RI2550000 AC8 AC4 24 AC6 24 AC8 24 AC6 AC12 AC12R AC3RM24DL 5RI2560000 AC4 AC4R 5RI3440000 AC12 AC12R 5RI3450000 AC6RM24 DL ...

Page 11: ...2730000 AC4R AC6R AC8R AC12R 5RI2600000 AC4 AC6 AC4R AC6R AC4A24 AC6A24 AC6RM24DL 5RI2610000 AC3RM24DL 5RI2620000 AC8 24 5RI2630000 AC4 AC6 AC8 AC8R AC4R ACA 24 AC6 24 AC6R AC6RM24DL 5RI2640000 AC8A 24 AC8A 24M 5RI2570000 ACER 5R2580000 ACER 5RI2590000 ACER 5RI2620000 AC8 AC12 AC8R AC12R 5RI2650000 AC3RM24 DL 5RI268000 ACER SIMPLY ...

Page 12: ...l and garage doors and gates Safety in the usage of motorised doors Requisites EN 60204 1 1997 Machinery safety Electric equipment of the machine Part 1 general rules EN 60950 Information technology equipment Safety Part 1 General requisites ETSI EN 301489 3 2001 Electromagnetic compatibility for radio equipment and appliances EN 300220 3 2000 Radio equipment and systems short band devices Technic...

Page 13: ...RG1R UNI DL RG1R DL CONTROL UNIT FOR AUTOMATIONS FITTED WITH 230 V MOTORS INSTRUCTIONS AND WARNINGS FOR INSTALLATION USE AND MAINTENANCE ...

Page 14: ... OHFWURQLF FRQWURO XQLW 1 5RI122000 2 2AS3710000 Components and devices of a typical automation STANDARD INSTALLATION ...

Page 15: ...A L B K C A L B E U L B E U L B N W O R B N E E R G D E R C N PHOTO1 PHOTO STEP CLOSE OPEN STOP COMMANDS COMMON RG58 50ohm AERIAL N C N O N O N O N C N C 1 2 6 7 8 9 10 11 12 14 15 16 17 18 19 L1 L1 L2 230 Vac 24 Vac 3W max INDICATOR LIGHT EXIT 24 Vac 200 mA max 230 Vac 25W max 230 Vac 40W max COUTESY LYGHT FLASHING R O T O M R O T I C A P A C 230V 0 16 24 K C A L B E G N A R O K C A L B E U L B E...

Page 16: ...flash Secs PHASE 2 PROGRAMMING THE TRAVEL a Press start or 5 seconds the 5 LEDs will light and then start flashing b Press and the gate starts rolling if it open press again o the movment The first activated limit switch has to be the one of the closing system The automation will perform in sequence a closure 1 an opening 2 a closure 3 Once programming is complete the two green LEDs will flash and the...

Page 17: ...to the following cycles SEMI AUTOMATIC MODE Open stop close stop Automatic mode open pause close pause 230Vac 50 Hz power supply L 2 L 1 N C normally closed contact NO normally open contact PHASE 3 AACKNOWLEDGMENT OF THE TOTALOPENING RADIOCOMMAND a Press the green led SX will light and the red one A will switch on b Hold down the key P1 on the radio control until all five LEDs light c Wait 25 secon...

Page 18: ...LE 24 B1 ORANGE CABLE COMMON FC1 FC2 ATTENTION the connections pre wired by the manufacturer may not be altered under any circumstances 1 1 2 Indicator LEDs There is a row of 6 LEDs on the right hand side of the board under the terminals These LEDs are lit when the corresponding signal is present For N C inputs STOP PHOTO1 and PHOTO the corresponding LEDs L7 L11 and L12 are normally on For the N O...

Page 19: ...ns between the control unit motor encoder and transformer have already been performed by the Manufacturer Once the connections to the control unit have been made the Fitter must use bands to join adjacent wires into groups of 2 3 or 4 in order to prevent them coming away from the terminal board bands must be attached as close as possible to the terminals no more than 10mm away taking care not to d...

Page 20: ...mitter has been deleted To exit wait 25 seconds or push the radio To exit wait 25 seconds or push the radio icon button once icon button once Secs Secs Secs DELETING ALL RADIO TRANSMITTERS DELETING ALL RADIO TRANSMITTERS Press the radio icon button top left for 5 Press the radio icon button top left for 5 seconds The left green led will light and seconds The left green led will light and start fla...

Page 21: ...NS 1 NO FUNCTIONS ACTIVATED Block of appartment Step by step in opening Modifies the function in OPENING STOP CLOSING STOP Automatic 2 Steps OPENING CLOSURE Input Stop becomes PHOTO2 the photocells intervenes in opening with brief invertion CLOSING PASSING BY passing by the photocells PHOTO the automation closes after 5 5 LEDS Preflashing Soft Start OPTIONS 2 OPTION MENU 2 Press the option button ...

Page 22: ... with an obstacle detection system The automation inverts its movement when it strikes an The automation is fitted with an obstacle detection system The automation inverts its movement when it strikes an obstacle during the opening and closing phases obstacle during the opening and closing phases 1 During the closure phase if the control unit identifies an obstacle the automation inverts the motion ...

Page 23: ... or arises frequently it is necessary to call the assistance service Try to perform a complete two way travel at reduced speed and with persistent commands If the problem persists or arises frequently it is necessary to call the assistance service N B Obstacle detection sensitivity regulation is described in the ADJUSTMENTS chap Check the phototest setting and try to give another command to repeat...

Page 24: ...is manual must always be observed when installing connecting adjusting testing and setting the control unit The Manufacturer declines all responsibility for damage or injury caused by non observance of the instructions contained in this manual The Manufacturer declines all responsibility for damage and faults to the control unit caused by non observance of the instructions contained in this manual...

Page 25: ...neral mechanical and electrical diagram risk analysis and solutions adopted for eliminating or reducing risks manuals of the individual components list of the components used instructions for use and warnings concerning use by the owner system maintenance record declaration of the system s CE conformity b Fix a CE marking plate to the gate bearing at least the following information Name and addres...

Page 26: ...person with a similar qualification in order to avoid risks Do not perform technical or programming modifications on the control unit Operations of this type may cause malfunctions and or risk of accidents The manufacturer declines all responsibility for damage caused by products that have been modified In the event of intervention of automatic or fuse switches before restoring function conditions...

Page 27: ...rised doors testing methods EN 12453 Industrial commercial and garage doors and gates Safety in the usage of motorised doors Requisites EN 60204 1 1997 Machinery safety Electric equipment of the machine Part 1 general rules EN 60950 Information technology equipment Safety Part 1 General requisites ETSI EN 301489 3 2001 Electromagnetic compatibility for radio equipment and appliances EN 300220 3 20...

Page 28: ...http www homelife net au Telefax 61 2 9600 8882 Telephone 61 2 9607 4100 Factory 19 5 Lyn Parade Prestons NSW 2170 Address ...

Reviews: