background image

19

Installation Notes:

The 

HRV 

will 

produce 

some 

condensation  while  running.  This 

water  should  flow  into  a  nearby 

drain,  or  be  taken  away  by  a 

condensate 

pump. 

The 

HRV 

cabinet  has  pre-punched  holes  for 

the  drain (see below).

Drain

 

Connections

Electrical

 

Connections

Electrical

 

Connections

It  is  recommended  that  a  licensed  electrician  make 

all electrical  connections.  It  is  very  important  that  the 

unit  be properly  grounded. 

The circuit must be sized to 

handle the F.L.A. indicated on the name tag of the unit.

DRAIN

SPOUT

TAPE

TO 

DRAIN

TEE

CONNECTOR

DRAIN

SPOUT

HRV CABINET

The

 

HRV

 

and

 

all

 

condensate

 

lines

 

must

 

be

 

installed

 

in

 

a

 

space

 

where

 

the

 

temperature

 

is

 

maintained

 

above  the 

freezing  point  or  freeze

 

protection

 

must

 

be

 

provided.

Drain

 

trap

 

and

 

tubing

 

MUST

 

be

 

below

 

bottom

 

of

 

door

 

with

 

1/4"

 

per

 

foot

 

downwards

 

slope

 

away

 

from

 

unit.

CAUTION

Forming

 

the

 

“P”

 

Trap

CAUTION

The

 

HRV

 

is

 

designed

 

to

 

operate

 

with

 

ducting.

 

When

 

first

 

starting

 

the

 

HRV,

 

measure

 

the

 

amp

 

draw

 

to

 

each

 

motor

  at  each  speed 

to

 

ensure

 

it

 

is

 

operating

 

at

 

or

 

below

 

the

 

max

 

rating.

Maximum AMP Rating

HIGH

MED.

LOW

1200 POOL

1

9.4

6.0

4.5

700 POOL

4.5

In 

order 

to 

prevent 

electric 

shock 

when  cleaning  or  servicing  the  HRV,  it  is 

extremely  important  to  confirm  the  polarity 

of  the  power  line  that  is  switched  by  the 

safety  (disconnect)  switch  whose  control 

arm  is  located  on  the  outside  of  the 

electrical  control  box  area.  The  hot  line 

(black)  is  the  proper  line  to  be switched. 

To  confirm  the  proper  polarity,  use  a 

voltmeter or test lamp to make sure there is no 

power  after  the  switch  when  the  door  is 

open.  Check  between  that  point  and  ground 

(on  the  cabinet).  This  must  be  done  as 

occasionally  some  buildings  are  improperly 

wired.  Always  make  sure  the  HRV  is  properly 

grounded.

WARNING

Installation Steps:

1) Insert the drain spout through the hole in the drain pan.
2) Hand tighten the lock nut which holds the drain spout in place.
3) Construct a P-trap using the plastic tee connector.
4) Cut two lengths of 1/2 in drain hose (not included) and connect the other

ends to the two drain spouts.

5) Position the tee connector to point upward and connect the drain line.
6) Tape or fasten base to avoid any kinks.

7) Slowly  pour  water  into  the  drain  pan  of  the  HRV  after  the  drain

connection  is  complete.  This  is  to  ensure  that  the  drain  assembly  is

functional  and  also  creates  a  water  seal  which  will  prevent  odours  from

being drawn up the hose and into the fresh air supply of the HRV.

CAUTION

Summary of Contents for 1200 POOL

Page 1: ...POOL 1200POOL Operation and Installation Manual Lifebreath Pool Room HRVs provide fresh clean air without sacrificing the savings of your energy conserving home The aluminum cores of the HRV provide effective and efficient heat recovery and air exchange Models 700POOL 1200POOL ...

Page 2: ...erse Installation of the HRV 24 25 Never install an HRV in a situation where its normal operation lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment It is always important to assess how the operation of any HRV may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc Do not apply electrical po...

Page 3: ...er the system Outside air is prevented from entering the HRV during recirculation by the supply damper closing off The exhaust fan to the outside is shut off during this recirculation mode Outside air does not enter the system again until the pool room humidity exceeds the setpoint of the dehumidistat HRV Aluminum Core A Heat Recovery Ventilator HRV is designed to provide fresh air into a building...

Page 4: ...eed Fan setting Low Medium High 4 wire connection 20 gauge wire minimum CORES Modular 2 section patented aluminum heat recovery cores arranged for efficient counter flow ventilation MOTORS Two PSC 3 speed single shafted 120 VAC 4 5 Amps each 9 total on high speed HP 1 4 1450 RPM Watts total on high speed 1032 MCA 11 3 MOP 15 FILTERS Washable air filters in exhaust and supply air streams BLOWERS Sl...

Page 5: ...mm H MOUNTING Unit to be set on support brackets hung by threaded rod type apparatus brackets and rods not provided CASE Unit has front and back access doors and electrical panel can be switched to either side giving installer flexibility in duct direction 20 gauge prepainted galvanized steel G60 for superior corrosion resistance Insulated with elastomeric insulation where required to prevent exte...

Page 6: ...ng flow Rate factor depending on the indoor air temperature outdoor temperature and room relative humidity Flow Rate Factor 21 70 Evaporation rate X Flow Rate CFM square foot of water surface area 0 052 X 21 70 1 12 4 Multiply the value in step 3 by the area of the pool X Value for step 3 CFM Area of pool 512 X 1 12 573 Calculating the Ventilation Rate for the Pool Room Spas Hot Tubs must be consi...

Page 7: ... 0 053 0 082 0 073 0 064 0 094 0 085 0 076 0 107 0 098 0 089 0 121 0 112 0 103 78 0 059 0 049 0 039 0 069 0 059 0 049 0 080 0 070 0 060 0 091 0 082 0 072 0 104 0 095 0 085 0 118 0 109 0 099 80 0 056 0 046 0 035 0 066 0 056 0 045 0 077 0 067 0 056 0 089 0 079 0 068 0 102 0 091 0 081 0 116 0 105 0 095 82 0 053 0 042 0 031 0 063 0 052 0 041 0 074 0 063 0 052 0 086 0 075 0 064 0 099 0 088 0 077 0 113 ...

Page 8: ... 39 40 29 80 24 00 34 70 26 40 21 30 30 70 23 50 19 00 27 30 21 00 17 00 15 56 20 41 00 32 20 48 50 35 80 28 30 42 10 31 40 25 00 36 80 27 60 22 10 32 40 24 50 19 60 28 60 21 70 17 50 20 63 40 44 70 34 50 53 70 38 50 30 00 46 00 33 50 26 30 39 70 29 30 23 10 34 60 25 70 20 40 30 30 22 70 19 10 25 74 90 50 10 37 60 61 70 42 50 32 40 51 80 36 40 28 10 44 00 31 50 24 50 37 80 27 40 21 50 32 70 24 10 ...

Page 9: ...be mounted on an equipment platform providing the drain hoses are clear and there is sufficient space to open the doors for servicing Install the drain pans in the bottom of the HRV so the drain connections protrude through the holes provided Use drain hoses with hose clamps to connect the drain pan outlets to a floor drain or standpipe Make sure the drain line slopes down to the outlet If this is...

Page 10: ...es of contaminants such as automobile exhaust fumes gas meters garbage cans containers etc not exposed to prevailing winds The outside perimeter of the weatherhood must be caulked to prevent leakage into the building The design and size of the weatherhoods or louvers chosen by the installer must allow for adequate free area Water and snow penetration of the system is minimized when the airflow doe...

Page 11: ...e of room EXPOSED WALL Min 10 0 HRV Typical Duct Layout Sketch 1 Sample Duct Layout 1 System Installation It is necessary to design and size the duct distribution system for both the supply and the exhaust air streams Proper duct design will Minimize air flow requirements Ensure a comfortable environment by using reheat if required Optimize humidity control including eliminating condensation on wi...

Page 12: ...le air from opposite side of room Typical Duct Layout Sketch 2 Sample Duct Layout 2 System Installation It is necessary to design and size the duct distribution system for both the supply and the exhaust air streams Proper duct design will Minimize air flow requirements Ensure a comfortable environment by using reheat if required Optimize humidity control including eliminating condensation on wind...

Page 13: ...ated when outside temperatures drop below 27 F 3 C A motor driven damper door mechanism opens the pool and defrost air port and closes off the supply air from outside port This defrost cycle operates for about 3 minutes and then the damper reverts to its previous run time position 2 RECIRCULATION MODE TO POOL ROOM EXHAUST TO OUTSIDE FROM POOL ROOM FROM POOL ROOM Ø FRESH AIR FROM OUTSIDE DAMPER CLO...

Page 14: ...d develops in one of the devices Stale Air Return System Fresh Air Supply System Adjustable Grilles The stale air return system is used to draw air from the points in the building where the highest humidity levels exist Balancing dampers and or adjustable grilles are recommended on all return air lines which are used during installation to help balance the draw from different areas of the pool roo...

Page 15: ...rcuit board Switch T37 and T39 on the Aircom circuit board Switch T37 red wire and T39 yellow wire on the Aircom circuit board if you wish to reverse the Supply Air From Outside and Pool and Defrost Air ports This illustration shows the factory configuration T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 Contact 1 N 0 COM N C N 0 COM N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 N C RED Y...

Page 16: ...T HIGH OFF OFF OFF MED LOW Optional 3 Speed Control Part 99 500 Connect to R W Y and G on Thermostat O G Y W R C Thermostat 24V Jumper Wire HIGH MED LOW Jumper Wire Placement on Micro Processor Board SPEED High R W Medium R Y Low R G JUMPER T18 T5 T13 C4 T17 T19 T1 T2 T3 T4 T6 T14 T15 T16 C3 C2 C1 RELAY Fan Hi Fan Med Fan Low FEED Line Ligne Neutral Neutre T20 CHASSIS T11 T12 T44 N O N O N O N O C...

Page 17: ...ss and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level is lower than the setting Refer to the unit s Operation ...

Page 18: ...n the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate to the Back Plate Figure B Note Be careful to correctly align the Face Plate to avoid damaging the Face Plate Contact Pins 10 Insert the Operating Instructions Card into the control Figure A 11 Connect the 3 wire 20 gauge min 100 ft length max to the digital controls termin...

Page 19: ...der to prevent electric shock when cleaning or servicing the HRV it is extremely important to confirm the polarity of the power line that is switched by the safety disconnect switch whose control arm is located on the outside of the electrical control box area The hot line black is the proper line to be switched To confirm the proper polarity use a voltmeter or test lamp to make sure there is no p...

Page 20: ...nit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a manometer capable of reading 3 digits of resolution The tube coming out of the top of the pitot is connected to the high press...

Page 21: ...e any of the other DIP switch settings Only available when unit is operating in ventilation mode Factory Setting DIP Switch 8 OFF The HRV enters defrost mode when outdoor temperatures drop below 27 F 3 C The factory defrost cycle is 4 minutes defrost with a 30 minute run time Increased Defrost Time DIP Switch 8 ON Cooler climates may require a more aggressive defrost cycle Positioning DIP switch 8...

Page 22: ...temporarily preventing its removal In most cases all the core requires is a wash in a mild detergent and warm water to completely clean it Do not use harsh chemicals as their use may cause corrosion in the HRV The time required between each core service depends on the application in which the HRV is installed Service may be required as often as one month two months or at the very least cleaned eve...

Page 23: ...drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slope to it 1 8 1 4 per foot The drain line itself should have a P trap in it below the HRV which is to be filled with water to prevent odors or gases from entering back into the unit Duct Work It is a good idea to inspect du...

Page 24: ...rt the shim around the damper rod ensuring it is placed on the opposite side of the rod from the set screws Both of the set screws should screw directly into the damper rod not the shim 17 Prior to tightening the set screws ensure proper alignment of the damper door such that it is evenly spaced over the port collars providing a good seal in both directions 18 Once alignment is confirmed tighten t...

Page 25: ...the lower blower motor wires through the hole in the divider panel into the electrical box 29 Route upper motor wires into the electrical box 30 Route damper motor wires into e box and connect the motor wires to the circuit board relays and capacitors using wiring diagram found in manual for reverse installations 31 Connect damper motor wires to circuit board using wiring diagram found in manual f...

Page 26: ...ior hoods or vents remove and clean filter remove and clean core check and open grilles open and adjust dampers have electrician check supply voltage at house check duct installation increase the speed of the HRV have contractor balance HRV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occu...

Page 27: ...27 Wiring Diagram Models 700 1200 POOL ...

Page 28: ...ects please contact AIRIA BRANDS INC 511 McCormick Blvd London Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labor required to install any replacement part s shall be dealt with at the option of the customer in either of the following ways a the customer may supply labor at their own expense or b if the product was purch...

Page 29: ...29 ...

Page 30: ...30 ...

Page 31: ...31 ...

Page 32: ...info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 POOL 100516 ...

Reviews: