A8 / A8P Installation Manual

2

3

 

Wiring the A8 Board

h

 

Remove all AC power from the FPA system before adding or replacing an A8 board

.

Description

The A8 simple distribution accessory provides eight zones of 

fused or PTC-protected AC distribution with no built-in con-

trol features. The A8 is capable of distribution of one or two 

AC voltages.  Each zone output is selectable for either input 

voltage by zone.

Specifications

Input

Voltage

16 - 28VAC nominal ±15%

Current

20A maximum

Standby Current 65mA

Output

Voltage

Same as input

Current (A8)

3A

Current (A8P)

2.5A (Class 2 Power Ltd) 

Fuse

 (A8 Only) 3A ATM automotive style

Size

A8/A8P

4.00" x 2.50" x 1.0" 

(102mm x 64mm x 25 mm)

Weight

A8/A8P

0.15lb (0.07kg)

Regulatory Information

The equipment discussed within this manual has been tested 

to the following standards:
•  UL294, UL2044
•  CSA C22.2 #107.1

Mounting the A8 Power Distribution Accessory

Mounting of the board to an enclosure is via the four 

snap-in standoffs supplied.
1.  Locate the appropriate 

mounting holes in the 

enclosure and snap 

the standoffs into the 

holes.

2.  Align the board mount-

ing holes with the 

standoffs (be sure the PC board is properly oriented) 

and snap the board onto the standoffs.

A8

OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8

A8

B1
B2

B1
B2

BR

BR

Each of the 

B1, B2, BR,

 busses has 

two connectors

. These 

connectors may be used interchangeably.

First AC voltage continues to 

other accessories

Second AC Source continues to 

other accessories

BR continues to other accessories

AC OUT terminals to devices to be powered

BR in from System

Input from First

AC voltage source

Input from Second 

AC source (optional)

Required Connections
Optional Connections

Summary of Contents for FlexPower A8

Page 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 004 Rev A06 A8 A8P Installation Manual ...

Page 2: ...ent discussed within this manual has been tested to the following standards UL294 UL2044 CSA C22 2 107 1 Mounting the A8 Power Distribution Accessory Mounting of the board to an enclosure is via the four snap in standoffs supplied 1 Locate the appropriate mounting holes in the enclosure and snap the standoffs into the holes 2 Align the board mount ing holes with the standoffs be sure the PC board ...

Page 3: ...e their BR fastons wired together for proper operation except for between the DC and AC sections of an FPX hybrid system 4 Output Selection Jumpers JP1 JP8 These jumpers select which voltage buss input is select ed for the output Jumper numbers correspond with the zone number e g JP1 is the jumper for OUT1 Possible settings are as follows Position 2 Left B2 Buss Position 1 Right B1 Buss Removed Di...

Page 4: ...er set in Position 2 will have a continuous 28VAC output This application shows dual A8 s for sixteen zone distribution The B1 input is connected to the blue lead 24VAC output of the FPA dual tapped transformer B2 input is connected to the orange lead of the FPA transformer for 28VAC output Any zone output with its jumper set in Position 1 will have a continuous 24VAC output Any zone output with i...

Page 5: ...5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 B1 B2 BR B1 B2 BR B1 B2 BR B1 B2 BR OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 JP1 2 1 JP2 2 1 JP3 2 1 JP4 2 1 JP5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 A8 Application Examples Typical 300VA 16 outputs with zone select 24 28V AC power ...

Page 6: ...AGE will occur JP1 2 1 JP2 2 1 JP3 2 1 JP4 2 1 JP5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 i OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 JP1 2 1 JP2 2 1 JP3 2 1 JP4 2 1 JP5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 B1 B2 BR B1 B2 BR B1 B2 BR B1 B2 BR A8 Application Examples Typical 600VA 16 outputs with zone select 24 28V AC power ...

Page 7: ...unication board used in FPO systems NL4 A11 NetLink network communication board used in FPO systems NLR A11 002 NetLink network communication kit remote reset used in FPA systems NS2 A11 003 Reset module board for use with NL1 RB2 A25 001 2A Relay 12VDC or 24VDC input range DP DT RB5 A25 002 5A Relay 12VDC or 24VDC input range DP DT RB8 A25 003 8A Relay 12VDC or 24VDC input range DP DT Hardware Or...

Page 8: ... its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In addition LifeSafety Power reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification LifeSafety Power FlexPow...

Reviews: