24
3.2.3
Direct control
The controlling of the motor is directly carried out by the control pendant.
Gear cap
Cable gland for
motorized trolley
Cable gland for
mains supply
Cable gland for
control cable
Brake contactor or current
contactor
Rectifier
Terminal block board
Cap for gear cover
Figure 19: Direct control
3.2.4
Low voltage control
The control occurs in a control circuit, which receives its 24 V control voltage by a control transformer.
Other control voltages are available on request.
If the control is equipped with an “emergency stop” in accordance with DIN EN 60204-32:2008, an additional
contactor is also loca
ted in the control box and the “emergency stop” button is fitted on the control pendant.
The control contactors are easily accessible on a console under the cap for control.
The limit switches for lifting and lowering are situated under the cap for brake.
Cable gland for
motorized trolley
Cable gland for
mains supply
Cable gland for
control cable (not shown)
Control transformer
Rectifier
Fuses secondary 1.25 A
and primary 1.25 A
Contactors
Terminal block board
Cap for gear cover
Figure 20: Low voltage control