LMIU 125/250/400W Mini Inverter

     

TROUBLESHOOTING GUIDE (PAGE 1 OF 2)

STATUS 

INDICATOR (LED)

TROUBLESHOOTING GUIDE

DISPLAY

DETAIL

SYMPTOMS

PROBLEM

CORRECTIVE ACTION

LED GREEN 
ON Steady, 
not flashing

Lamp load is on

None if unit is in normally on mode Unit is operating correctly

Lamp load is off

None if unit is in normally off mode Unit is operating correctly

Lamp load is OFF, but 
the unit is in normally 
on mode

The fuses are burnt

Replace the fuses after verifying that there is no 
short circuit in the load

-Lamp load is OFF
 

(if installation is

  normally OFF)
- Lamp load is ON
 (if installation is
  normally ON)

Power at primary AC input + 
battery discharged (at LVD) + no 
reaction with test button

- Remove the primary AC input + disconnect the
  b wait minimum 10 seconds
- connect the b connect the primary AC input
  => the unit will restart
- if the unit did not r call the technical support.

LED flashing 
GREEN/
ORANGE

Lamp load is ON

None if unit is in normally on mode 
+Nexus option

Unit is operating correctly. Unit is not commissioned 
to the Nexus system

Lamp load is OFF

None if unit is in normally off mode 
+Nexus option

Unit is operating correctly. Unit is not commissioned 
to the Nexus system

LED flashing 
GREEN/OFF

Lamp load is ON

None the unit is in test mode or is 
sampling load

Unit is operating correctly

Lamp load is OFF

Inverter switched OFF

Check the inverter ON/OFF switch => Turn it on.
Switch is located on the right side of the inverter 
module.

The output fuse is burnt

Replace the fuses after verifying that there is no 
short circuit in the load

LED steady 
OFF, not 
flashing

Lamp load is ON

No power at primary AC input + in 
emergency mode

Check the circuit breaker panel

Lamp load is OFF

No power at primary AC input + 
emergency mode stop (battery 
discharged)

Check the circuit breaker panel

- Lamp load is OFF 
  

(if installation is

    normally OFF)
- Lamp load is ON
 (if installation is
  normally ON)

Power at primary AC input + 
battery discharged (at LVD) + no 
reaction with test button

- Remove the primary AC input + disconnect the
  b wait minimum 10 seconds
- connect the b connect the primary AC input
  => the unit will restart
- if the unit did not restart, call for technical support at
  1-(888)-552-6467.

LED RED 
steady ON

Battery Disconnect 
Error

No battery installed in the unit

Install the battery following the installation guide

Summary of Contents for LMIU 125W

Page 1: ...onal Electrical Code and local regulations 12 The LMIU contains potentially hazardous voltages Installation maintenance and service work should be performed by qualified and trained personnel 13 Elect...

Page 2: ...TH NORMAL AND EMERGENCY SOURCES BY TURNING OFF THE A C BRANCH CIRCUIT AND BY DISCONNECTING THE BATTERY CAUTION BEFORE INSTALLING MAKE CERTAIN THE A C POWER IS OFF NOTE THE BATTERY S ARE SHIPPED SEPARA...

Page 3: ...specting the operating voltage All remote circuitry is to be wired in accordance with Article 700 of the National Electric Code Do not exceed the total rating of the Mini Inverter Unit is rated at max...

Page 4: ...e same color in each pole on the terminal block See Figure on side c Leave a minimum of one inch 25mm between the live voltage cabling and the unsheathed low voltage data cabling NOTE NO WIRING IS REQ...

Page 5: ...e of 20 to 30 C 68 to 86 F their life expectancy is 8 to 10 years However as stated above the equipment must be tested for a minimum of 90 minutes once per year When the batteries will no longer opera...

Page 6: ...tched Neutral Ground Line see note 3 see note 3 Wall Switch Normally ON Lighting Load Output Wiring Triac Dimmer Device Fluorescent LED Incandescent FIGURE 2A WIRING DIAGRAM SWITCHED NORMALLY ON LOAD...

Page 7: ...PUT POWER terminals 4 DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD NEUTRAL Un Switched see note 3 Line 120Vac Neutral 120V Neutral 120Vac Ground 0 10V FIGURE 2D WIRING DIAGRAM UN SWITCHED NORM...

Page 8: ...switch for at least 6 seconds The reset also initializes the main counter This renewal takes place to compensate for system variations when the unit ages Renewal is not allowed if there is a lighting...

Page 9: ...isabled during a power failure in order for the load to provide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergen...

Page 10: ...not commissioned to the Nexus system Lamp load is OFF None if unit is in normally off mode Nexus option Unit is operating correctly Unit is not commissioned to the Nexus system LED flashing GREEN OFF...

Page 11: ...the batteries LED Flashing RED 2 times every 6 seconds Charger Failure Error Charger not working Reset the unit see page 4 and if the same error is displayed replace the charger board LED Flashing RED...

Page 12: ...CT CUSTOMER SERVICE FOR REPLACEMENT PARTS SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service for current warranty information All information and specifications contained in t...

Reviews: