RLPC MODBUS Register Map v1.44
248083227-1 Rev 8
B-5
Alarm Mode (40037) defines the type of calculation performed to
define an alarm condition. Alarm Mode = 0 corresponds to
conventional threshold alarming; channel bit set if threshold exceeded
for that given channel.
Alarm Parameter (40038) defines additional parameters that may be
needed in defining an alarm mode.
Device Status
The Device Status register (40003) displays the current status of the
device.
Command
Register
The Command Register (40002) is used to make the device perform an
action. The register performs an action when an integer value is written
to it. The action is completed when the device sends a MODBUS
response. When this register is read, it always returns a zero.
Table B-4 Device Status
Bit
Description
0
RUNNING:
Set when a start command is executed
remotely via Command 9 (manual start) or Command 11
(instrument start) or through the user interface. The flag
will remained set until a stop command is executed.
1
SAMPLING:
This is set only when the instrument is
actually sampling data that is to be recorded. Caution
must be used in sending a command during this time that
may invalidate current sample.
2
NEW DATA:
Set to 1 to indicate that a new data record
has been recorded and it hasn't been read via modbus yet.
When a data record has been read via modbus (registers
30001 to 30999), then this flag is reset to zero.
Table B-5 Command Register
Value
Action
1
Saves all writable 4xxxx register values to the EEPROM.
2
Reserved for future use.
3
Clears the Data Buffer. Record count is set to zero.
Summary of Contents for RLPC 0.1m
Page 1: ......
Page 2: ...00...
Page 3: ...Lighthouse Worldwide Solutions REMOTE Liquid Particle Counter MODBUS Output Operating Manual...
Page 6: ......
Page 14: ...Lighthouse REMOTE Liquid Particle Counter MODBUS Output Operating Manual ii 248083227 1 Rev 8...
Page 24: ...Lighthouse REMOTE Liquid Particle Counter MODBUS Output Operating Manual 2 8 248083227 1 Rev 8...
Page 32: ...Lighthouse REMOTE Liquid Particle Counter MODBUS Output Operating Manual 3 8 248083227 1 Rev 8...
Page 112: ...Lighthouse REMOTE Liquid Particle Counter MODBUS Output Operating Manual D 2 248083227 1 Rev 8...
Page 117: ...00...
Page 118: ......