Document 36 II Stormaster Version 1.02 © Copyright 2008 LPI
17
Hauling the HVSC Downconductor
Place the HVSC downconductor cable drum close to where it is to be installed.
• Make sure that the cable drum is in a servicable condition.
• Check that the correct length of HVSC downconductor has been supplied. The length of
HVSC will be marked on the drum.
• If the HVSC downconductor has been upper terminated on the outside of the drum, then
the HVSC downconductor will need to be hauled up the structure with the drum staying
on the ground.
• If the HVSC downconductor has been upper terminated on the inside of the drum,
then the drum has to be taken to the top or near the top of the structure, then the HVSC
downconductor can be hauled downwards from the drum to the ground.
Figure 10.