26
Document 36 II Stormaster Version 1.02 © Copyright 2008 LPI
1. Remove the outer sheath for a length of 15cm from the lower end of the HVSC by cutting
radially around HVSC cable with the supplied insulation friction cutting tool. (This is less
likely to damage individual copper conductors than by cutting radially with a knife).
The lengthwise cut can be completed with a knife.
2. Remove the clear binder tape (2nd layer) for a length of 15cm from the end of the HVSC,
this will expose the outer screen copper conductors as shown in Figure 17.
3. Bend outer screen conductors back without damaging them. For a length of 5cm from
the end of the HVSC, remove XLPE insulation (4th layer) and inner binding tape (5th
layer) to expose inner screen copper conductors. Be sure not to remove outer
screen conductors in this step. It is recommended to use the insulation friction cutting
tool in this step.
4. Bend inner screen conductors back without damaging them. For a length of 5cm from
the end of the HVSC, remove the inner PVC filler core under the inner screen copper
conductor leaving the inner screen copper conductor in place.
Figure 17.
Figure 18.