Document 36 II Stormaster Version 1.02 © Copyright 2008 LPI
27
5. Bunch together both inner and outer screen conductors. If connecting directly to the
earth system as per figure 21, the bunched conductors should be connected to the earth
rod clamp and the clamp tightened holding the conductors firmly in place. To avoid
oxidisation of this connection, seal it using the waterproofing tape as provided in the kit.
6. If terminating the lower end of
the HVSC to a bus bar, bunch
together both inner and outer
screen conductors, crimp them
together in the 95m
2
crimp lug
provided using a compression
or mechanical crimping tool and
connect the bus bar as per
Figure 20.
To Earthing System
Compression
Lug
HVSC
LSR1
Copper
Bus Bar
Figure 19.
Figure 20.