28
Document 36 II Stormaster Version 1.02 © Copyright 2008 LPI
Earth Rod
Earth Rod
Waterproofing
Tape
Earth Rod Clamp
HVSC
Downconductor
HVSC
Downconductor
Ground Level
STEP 1.
STEP 2.
Figure 21.
Lower Termination of Conventional
Downconductor to the Lightning Earth
• If installing stranded copper cable as a downconductor then the lower end should be
connected to the lightning earth through the use of an earth rod clamp and then wrapped
with waterproofing tape to avoid oxidisation.
• If installing copper tape (25mm x 3mm) as a downconductor then the lower end should
be directly connected to the lightning earth through the use of a suitable earth rod clamp
and then wrapped with waterproofing tape to avoid oxidisation.