EM58 – HS58 - HM58 MODBUS TCP/IP
4.1.2 P1 Port 1 and P2 Port 2 connectors (Figure 1)
Two M12 4-pin female connectors with D coding are used for Ethernet
connection through port 1 and port 2.
Description
Pin
Tx Data +
1
Rx Data +
2
Tx Data -
3
Rx Data -
4
The ports are equal and interchangeable - if only one connection is required,
either port can be used. The Ethernet interface supports 10/100 Mbit/s, full/half
duplex operation.
4.1.3 Network configuration: topologies, cables, hubs, switches -
Recommendations
Using Ethernet several topologies of connection are supported by MODBUS
TCP/IP networks: line, tree, daisy-chain, star, … Furthermore MODBUS TCP/IP
networks can be configured in almost any topology in the same structure.
The connection of the encoder can be made directly with a network card or
indirectly with a switch, hub or company network.
Cables and connectors comply with the IEEE 802.3 Ethernet specifications.
If you use a direct connection to a computer/controller without network
components in between, you need to use a standard, “straight” network cable
(not a crossover cable).
You need at least a CAT-5 cable (category 5) to get a data transfer rate up to
100 Mbit/s. If there is a network component in the network which does not
provide fast Ethernet, the encoder will automatically switch down to 10 Mbit/s.
Standard Ethernet cables commercially available can be used.
For complete information please refer to IEC 61918, IEC 61784-5-13 and IEC
61076-2-101.
To increase noise immunity only S/FTP or SF/FTP cables must be used (CAT-5).
The maximum cable length (100 meters) predefined by Ethernet 100Base-TX
must be compulsorily fulfilled.
Regarding wiring and EMC measures, the IEC 61918 and IEC 61784-5-13 must
be considered.
For a complete list of the available cordsets and connection kits please refer to
the product datasheet (“Accessories” list).
4.2 Ground connection
To minimize noise connect properly the shield and/or the connector housing
and/or the frame to ground. Connect properly the cable shield to ground on
user's side. Lika's EC- pre-assembled cables are fitted with shield connection to
the connector ring nut in order to allow grounding through the body of the
MAN EM58_HS58_HM58 MT E 1.1.odt
Electrical connections
26 of 104