RD4 CANopen®
deceleration are set in objects
For a detailed description of jog control see on page 26.
Stop
bit 2
If set to “=1” the Slave is allowed to execute the movements
as commanded. If, while the unit is running, this bit
switches to “=0” then the Slave must stop executing the
deceleration procedure set in
. For
an immediate halt in the movement, use bit 7
Alarm reset
bit 3
Setting this bit to “1” causes the normal work status of the
device to be restored. This command is used to reset an
alarm condition of the Slave but only if the faulty condition
has ceased. Using SDO messages you can read further
information about the alarm in the index
Please note that should the alarm be caused by wrong
object values (
) normal work status
can be restored only after having set proper values.
alarm cannot be reset.
Incremental jog
bit 4
If set to “=0”, the activation of bits
bit to 1 the incremental jog function is enabled, that is: the
activation of bits
execution of a single step toward positive or negative
direction having the length, expressed in pulses, set next to
the
and waits for another issue.
bit 5
Not used.
Start
bit 6
If set to “=1” device moves in order to reach the set target
position. For a complete description of the position control
see on page 25. For any information on target position see
Emergency
bit 7
This bit has to be normally high (“=1”), otherwise it will
cause the device to stop immediately. For a normal halt (not
immediate) which respects the set deceleration see above
bit 2
MAN RD4 CB E 1.5
CANopen® interface
39 of 72