RD4 CANopen®
WARNING
Following an attempt to set the
Transmission Type
to 0, the PDO
message is not sent; following an attempt to change the
Transmission
Type
to any other value that is not supported by the device, an abort
message (abort code = 0609 0030h:
Value range of parameter
exceeded
) is generated.
NOTE
- Before altering the value of
COB-ID
it is compulsory to deactivate the receipt
of PDO1, then enter the new COB-ID value, finally activate again the receipt of
PDO1.
- PDO1 receipt can be activated (deactivated) by setting to “0” (“1”) the most
1400 Receive PDO Communication Parameter
sub 1
COB-ID
.
1600 Receive PDO Mapping Parameter 1
This object indicates the kind of parameter contained in the Receive PDO
message.
01
[Unsigned32, ro] Default = 3100 0020h.
02
[Unsigned32, ro] Default = 3106 0020h.
1800 Transmit PDO Communication Parameter 1
These objects contain the communication parameters of Transmit PDO.
01
COB-ID
of PDO1 [Unsigned32, rw]
Bit number
Value Meaning
31 (MSB)
0
PDO exists / is valid
1
PDO does not exist / is not valid
30
0
RTR allowed on this PDO
(not implemented)
1
no RTR allowed on this PDO
29
0
11-bit ID (CAN 2.0A)
1
29-bit ID (CAN 2.0B)
28 … 11
0
if bit 29 = 0
X
if bit 29 = 1: bits 28-11 of 29-bit-COB-ID
10 … 0 (LSB)
X
bits 10-0 of COB-ID
MAN RD4 CB E 1.5
Programming parameters