SFA-5000 • SFA-10000 DeviceNet
NOTE
If the scaling function is disabled (see the
to the “
Total hardware resolution
” - 1 (
23-01-2B Hardware number of turns
- 1).
If the scaling function is enabled (see the
23-01-11 Total measuring range
- 1.
WARNING
preset operation every time you change the
scaled values (
23-01-10 Resolution per revolution
attributes).
23-01-14 Delta for COS
(COS) mode connection is enabled, this parameter
sets the minimum interval between two I/O messages. Values too low could
cause the Bus network to saturate.
Default = 05h
23-01-18 Velocity value
[UDINT, ro]
This attribute represents the current speed detected by the position sensor and
calculated every 100 ms. The speed can be expressed in number of steps per
second or in revolutions per minute (see the following
attribute).
23-01-19 Velocity format
[USINT, rw]
This attribute identifies the engineering units for the velocity value. See the
previous
attribute.
00
: steps/s
number of steps per second
01: rpm
revolutions per minute
23-01-2A Hardware counts per revolution
[UDINT, ro]
WARNING
This attribute is active only if the
23-01-0E Scaling function control
is set to ”=00”; otherwise it is ignored and the system uses the custom values
MAN SFA_5000_10000_FD E 1.0.odt
DeviceNet interface
75 of 88