background image

 

 

   

                                                                             

Suzhou  Lily  Tech.  Co.,  Ltd. 

                                                                                                                                                                                                             

Page  1, Total  3  Pages

 

ZL-6290A (ZL-1000) Temperature Controller 

Instruction Manual   A1.3 

 

Introduction 

ZL-6290A (ZL-1000) has two outputs, one for cooling, one for heating, to regulate temperature to a set-point. 

It will judge heating or cooling mode automatically. 

 

Main Specification 

Sensor: NTC 

R

25

℃ 

= 10K, B

25/85

℃ 

= 3435K; R

25

℃ 

= 5K, B

25/50

℃ 

= 3470K   

Setting range: -50.0 ~ 99.0

, or -58.0 ~ 210.2

 

Display range: -50.0 ~ 99.9

, or -58.0 ~ 211.8

 

Terminal: 2*1.5mm

2

 or 1*2.5mm

2

 

Outputs: 

10A 

* 2, 250Vac (under pure resistance load) 

Working: -10~45

, 5~85%RH without dew   

Case materials: PC + ABS fire proof 

Protection level: IP65 (Front side only) 

Dimension: W78 x H34.5 x D71 (mm) 

Installation drilling: W71 x H29 (mm) 

Keypad and Display 

Key 

Key 

Function 

 

On/off 

Fast check Set-point 

Set 

Fast check Temperature Unit 

 

Down 

Fast check Hysteresis for Cooling 

 

Up 

Fast check Hysteresis for Heating 

 

LED lamp 

LED 

Function 

On 

Off 

Blinking 

Set 

Set parameter  Setting status 

 

Display fast check result 

(

SP, Unit, Hysteresis

Cool 

Cooling 

R1 is energized  R1 is de-energized  Delay protection for R1 (keep de-energized) 

Heat 

Heating 

R2 is energized  R2 is de-energized   

 

LED digit 

Display the information, 2Hz blinking. 

Warning 

Remark 

E1 

Sensor failure (Short or open) 

HH 

Temperature over the sensing up limit (

99.9

  or 211.8

℉)

 

 

Power up (reset) display 

Display the following information consecutively: all LED units, model name, software version 

 
 
 

 

Operation 

On/off line

 

Keep 

  key depressed for 5 seconds to switch online/offline. 

 

Fast check parameters 

When not in parameter setting status: 

Short press 

  to display heating hysteresis (

HYS-H)

 

for 

seconds, and the 

Set

 LED blinks in 2 Hz

.

 

Short press 

  to display cooling hysteresis (

HYS-C) 

for 

2

 seconds, and the 

Set

 LED blinks in 2 Hz

.

 

Short press “

S

” key to display temperature 

Unit

 (Fahrenheit or Celsius)

 

for 

seconds, and the 

Set

 LED blinks in 2 Hz

.

 

Short press 

  to display set-point (

SP)

 for 

2

 seconds, and the 

Set

 LED blinks in 2 Hz

.

 

 