7. Control Function Description 

7.1 Load Control 
Cooling Mode

 

●  When  the  temperature 

“Set  tempe”U22”,  and  the  load  has  stopped  for  “U10”, 

the load starts. 

●  When  the  temperature 

“Set  temperature”

-”U22”,  and  the  load  has  run  for  “U11”,  the 

load stops. 

For example:   

If set temperature is 18

℃,

U22

is 2

. When the temperature 

 20

, compressor starts. If 

the temperature

 16

℃,

compressor stops. The room temperature will be between 18±2

.

 

Heating Mode 

● When the temperature 

“Set temperature”

-”U22”, and the load has stopped for “U11”, the 

load starts. 

●  When  the  temperature 

“Set  tempe”U22”,  and  the  load  has 

run  for  “U10”,  the 

load stops. 

For example:   

If set temperature is 18

℃,

U22

is 2

. If the temperature

 16

℃,

compressor starts. If the 

temperature 

 20

, com

pressor stops. The room temperature will be between 18±2

.

 

7.2 Delay Load Output   

● After power supply, the load is able to start only after the time (U10) has passed. 

● After the load stops, it is able to restart again only after the time (U10) has passed. 

● After the load starts, it is able to stop only after the time (U11) has passed. 

7.3 Protection Running Mode When Room Temperature Sensor Fails

 

When the room temperature sensor fails, the system will automatically run into the protected 

running mode. In this mode, the compressor will run and stop with the period of 30 minutes. 

Compressor works for U12* 3 minutes, stops for 

30 - (U12* 3) 

minutes. 

For example: Set 

U12

  is 3

when the temperature sensor fails

compressor runs for 9 

minutes and then stops 21 minutes, move in circles. If U12=0, system stops when sensor fails 

7.4 Buzzer Function 

Buzzer sounds shortly for every key press. When confirming the parameter setting, it sounds 

longer. 3 short beeps means invalid. When the system comes wrong or external alarm input, 

the buzzer alarm function will be off if U62=0, or the buzzer continuous alarming if U62=1. 

After the system problem solved and disappears, press 

P

  key to stop warning. 

7.5 High-temperature and Low-temperature Warning 

● 

When the room temperature ≥ “set tempe “U50”, and the time reaches to “U52 or 

U53 or U34

”, high temperature warning starts. 

● 

When the test temperature 

 

“set tempe “U51”, and the time reaches to “U52 or 

U53 or U34

”, low temperature warning starts. 

7.6 Dry Contact Alarm Output   

When the sensor fails, high/low temperature warns, or external warning input, the dry contact 

relay opens and dry contact alarm outputs.

 

7.7 External Input Warning 

Summary of Contents for ZL-660A-R

Page 1: ...Buzzer alarm output Max high temperature or min low temperature exceed warning Sensor failure warning External warning input Dry contact alarm output RS 485 3 Size Specification 1 Front panel dimension 78 34 5mm 2 Drilling template 71 29mm 3 Whole machines dimension 78 34 5 71mm 4 Length of sensor s 3m including the sensor probe 4 Technical Specification Temperature Sensor NTC Setting Range 40 120...

Page 2: ...at temperature Keeping S pressed for 3 seconds to enter temperature setting mode The indicator or HACCP is on and the digital shows the set temperature Press key or to change the set temperature Keeping or pressed it will be adjusted quickly Press S the set temperature will be saved and leave the setting mode Or do not press any key for 30 seconds the device will leave the set mode without saving ...

Page 3: ...le 5 4 U20 Room temperature sensor calibration 9 9 9 9 0 5 U22 Temperature difference 0 1 10 0 The hysteresis of control 1 0 6 U50 High temperature warning deviation value to Max Temp 0 60 0 Disable 0 7 U51 Low temperature warning deviation value to Min Temp 0 60 0 Disable 0 8 U52 Over temperature warning delay time 1 180min 30 9 U53 First over temperature warning delay time after power supply 0 1...

Page 4: ...ture Sensor Fails When the room temperature sensor fails the system will automatically run into the protected running mode In this mode the compressor will run and stop with the period of 30 minutes Compressor works for U12 3 minutes stops for 30 U12 3 minutes For example Set U12 is 3 when the temperature sensor fails compressor runs for 9 minutes and then stops 21 minutes move in circles If U12 0...

Page 5: ... and Password Keep P and keys pressed for 5 seconds the device displays UnL press twice buzzer sounds system auto restores the default parameters and password 1111 8 Controller Installation 8 1 Warning Avoid installing the device in the following environment Relative humidity is greater than 90 or possibly dewing Strong vibration Possibility be dropped or within fog Exposed to eroding and pollutin...

Page 6: ...power devices Avoid direct contact with the internal electronic components After finish and check the electrical wiring layout before connect them to the device please follow this instruction Pay attention the electrical wiring diagram below wrong connection possibly damages the device and the system and may be dangerous to the user All security and protecting device for the equipments are necessa...

Page 7: ......

Reviews: