Do not block or restrict the inlet filters on the appliance. Restricted airflow will
result in reduced performance.
Keep means of electrical isolation accessible at all times.
A circuit breaker of type C, of suitable current rating should be fitted.
A Residual Current Device (RCD) of suitable current rating and min 30mA trip
level should be fitted. A short time delay AC-DC sensitive RCD is recommended.
Install this appliance on a level surface ensuring all vents are unobstructed. Any
adjacent partitions, walls or furniture must be of non-combustible material. To
avoid heat damage to the induction modules do not place this appliance next to
hot appliances such as ranges and griddles without following the minimum
distances stated, A 100mm, B 1000mm
– see Fig 1. Any heat damage through
not following this siting instruction will void the warranty of this appliance.