background image

IS 358  ECN 3592 

INSTALLATION INSTRUCTIONS. 

 

Before commencing installation of the appliance please take time to read the following 
installation instructions carefully. 
 
Parts protected by the manufacturer are not to be adjusted by the installer or user. 
 

Unit : J5 & J10. 

 
All appliances should be installed in accordance with BS 6173:1982, Code of practice for installation of gas 
catering  appliances,  taking  into  account  the  Gas  Safety  Regulations  1984  as  amended  by  the  Gas  Safety 
(Installation and Use)(Amendment) Regulations 1990 and the Health and Safety at Work Act 1974. 
It is mandatory that all appliances are installed and commissioned by a qualified and competent GAS SAFE 
registered gas fitter.

  

WARNING : Installation, service or repair of this appliance by non-GAS SAFE registered personnel 
will invalidate its warranty. 

 

VENTILATION

 

The area in which this equipment is to be installed should have sufficient fixed ventilation to comply with 
the  requirements  of  Approved  Document  J  in  the  1985  Building  Regulations.  It  is  recommended  that  a 
minimum Area of 450mm

2

 per 1kWh (3400Btu/hr) of total heat input must be allowed. Particular attention 

should be paid to the low level ventilation to ensure that the appliance has a good supply of clean, fresh air. 
 

INSTALLATION POSITION. 

To ensure a free flow of air around and behind the appliance, clear space of at least 100mm must be left at 
the rear between flue and the wall and to either side of the appliance or bank of appliances. There should be 
a minimum clearance of 750mm between the top of the appliance and any overlying shelf or ceiling. 
 
Any partitions, walls or kitchen furniture in close proximity should be of non-combustible materials. 
Installation should allow for a sufficient flow of fresh air for combustion air supply. 
It is recommended that this appliance is sited under an extraction canopy for the removal of combustion 
products. 
 
 

INSTALLATION COMMISSIONING. 

To ensure a full understanding of the correct operation of the appliance the following commissioning checks 
must be carried out before the appliance is handed over for use. 
 
All operators must know how to light, safely operate and shutdown the appliance. 
 
Although  all  Lincat  fryers  are  operationally  checked  during  manufacture,  commissioning  shall  include  an 
operational check of all controls and a calibration check on the thermostat.  This is carried out by filling the 
fryer to the correct level which is indicated on the batter plate, then setting the thermostat to 180 

C  

The oil temperature should be checked once the main burner has cut-out for the second time.  If necessary 
calibration of the thermostat should be made as per the instructions fou

nd under the “Servicing” section. 

 

 

 
GAS SUPPLY & CONNECTION

 

Check that the gas supply corresponds to that specified on the data plate. 
 
Connection is via a 1/2" bspt male thread on the back of the unit. If connection to the supply pipe is via a 
flexible  hose,  ensure  that  the  hose  used  is  suitable  for  commercial  catering  appliances.  The  supply  hose 
should be periodically examined and replaced as necessary. 
 

 

Summary of Contents for Silverlink 600 J10

Page 1: ...IS 358 ECN 3592 User and Installation Instructions Silverlink 600 Gas Fryer J5 and J10 Utensils Direct 01903 823888 Click here to order Lincat Gas Fryers...

Page 2: ...etting Heat input NOTES ON FRYING 7 8 Frying media Frying times Frying tips Oil capacity OPERATING INSTRUCTIONS 9 10 Operating instructions Preparation fo use Drainage and cleaning SERVICING 11 13 Gen...

Page 3: ...m us before you make your decision IMPORTANT Please read this page carefully before initially using the equipment WARNING This appliance must be installed and serviced by a registered engineer Whilst...

Page 4: ...de of the appliance or bank of appliances There should be a minimum clearance of 750mm between the top of the appliance and any overlying shelf or ceiling Any partitions walls or kitchen furniture in...

Page 5: ...its intended position whilst complying with the instructions as detailed in the User Document 2 Fit the upper brackets to the bottom of the unit using the screws provided 3 Loosely fit the lower brac...

Page 6: ...3 Adjustment is made via the valve s onboard governor which is situated centrally on the valve Fig 1 C 4 Remove the governor cap and turn the screw clockwise to increase the outlet pressure and anticl...

Page 7: ...d Used oil symptoms firstly indicate discolouration by darkening The oil becomes thin its fat content having become exhausted The next symptom is an unhealthy yellow foam which may appear on the surfa...

Page 8: ...is not placed into the oil FRYING TIPS 1 Always use a good quality oil or fat preferably oil which has a high breakdown temperature e g pure vegetable oil 2 Do not exceed the recommended cooking temp...

Page 9: ...in the off position Fig 3 1 Push in and turn anti clockwise to the Pilot position Fig 3 2 The knob will now depress further 4 Keeping the pilot control knob depressed press the piezo ignition button...

Page 10: ...er and provide the base of the tank with a coating of oil 5 Close the drain valve DRAINAGE 1 Always allow the oil to cool to a maximum 55 o C before draining 2 Remove the blanking nut Fig 2 e from the...

Page 11: ...ctions 3 Visually check the burner operation closely observing the flame picture and look for evidence of any debris or damage Remove burner and clean or replace as necessary 4 Visually check the inje...

Page 12: ...e pilot bracket and pull down 2 Undo the nut holding the thermocouple into the rear of the valve 3 Disconnect the wires from the interrupter terminal block 4 Replace the thermocouple 5 Reversal of the...

Page 13: ...afety Thermostat 1 Drain oil from fryer tank 2 Remove the thermostat housing and locate the thermostat 3 Remove the brass nut holding the thermostat to the housing 4 Disconnect the wires from the ther...

Page 14: ...lt system consists of a thermopile acting through the gas control via the control thermostat Heat from the pilot flame acting on the thermopile generates a 500 700 mV electrical potential This millivo...

Page 15: ...re stat for open circuit If all of the above are OK the control valve may be faulty Check pilot jet for blockage and clean where necessary Check supply Check thermocouple voltage minium 15mV Is the oi...

Page 16: ...Control Valve Technical Data Models J5 and J10 Dimensions J5 H1060 x W300 x D700 J10 H1060 x W600 x D700 Weight J5 34 8kg J10 69 5kg Inlet connection 1 2 BSP Natural Gas G20 Heat Input Gross 11 5 kWh...

Page 17: ...persons Note that for safe and efficient operation appliances need regular servicing Please quote both the model and serial numbers from the data plate attached to the unit Give brief details of the...

Reviews: